§ 16.16.500 — Services
Code of Ordinances of the City of Edmond, Oklahoma (Codified through Ordinance No. 4097, enacted August 10, 2026 (Supp. No. 40)) · Edmond Code of Ordinances tit. 16, § 16.16.500
Corpus is an independent public-information project, not the official City of Edmond website. Stable reference: corpuslaw.us/code/22af7692-9ee8-473a-9d36-80e4f4bfaf50
16.16.500 - Services.
NEC Section 230.82 item (3) is hereby amended to read as follows (remainder of items shall remain unchanged): (3) Meter socket disconnect switches located on the supply side ahead of the service meter socket nominally rated not in excess of 600 volts and not less than 480/277 volts that have a short-circuit current rating equal to or greater than the available short circuit, provided all metal housings and service enclosures are grounded in accordance with part VII and bonded in accordance with part V or Article 250. A meter disconnect switch shall be capable of interrupting the load served. The load break meter socket disconnect switch shall be the non-fused type and is not the service disconnecting means. The purpose of the meter socket disconnect switch is to facilitate meter change, maintenance, or disconnecting of the service.
(Ord. 3364, § 2, December 10, 2012).
Ask a question about Edmond law
Corpus searches the Edmond sections it holds and shows the ones that match, with their citations. Free, no sign-in.