17.04.605 - Fire Department Connections.

IFC Section 912.2 is hereby amended to read as follows: 912.2 Location. With respect to hydrants, driveways, building and landscaping, fire department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of fire department connections shall be located within 100 feet of a fire hydrant. The location of fire department connections shall be approved by the fire chief.

(Ord. 3584, § 11, January 23, 2017).