§ 17.04.706 — Appendix D - Fire Apparatus Access Roads - Multiple-Family Residential Developments

Code of Ordinances of the City of Edmond, Oklahoma (Codified through Ordinance No. 4097, enacted August 10, 2026 (Supp. No. 40)) · Edmond Code of Ordinances tit. 17, § 17.04.706

Corpus is an independent public-information project, not the official City of Edmond website. Stable reference: corpuslaw.us/code/f47a620e-6e2c-4b54-8617-e2fecaeb84f0

17.04.706 - Appendix D - Fire Apparatus Access Roads - Multiple-Family Residential Developments.

IFC, Appendix D, Section 106.3 is hereby amended as follows: D106.3 Remoteness. Where two fire apparatus access roads are required, they shall be placed a distance apart greater than or equal to one-half of the length of the maximum overall diagonal dimension of the property or area to be served, measured in a straight line between accesses. Exception: The distance between accesses may be reduced to one-third of the overall diagonal when all buildings served are sprinklered throughout with an approved automatic sprinkler system.

(Ord. No. 3962, § 18, July 10, 2023).