Sec. 9-15. - Code amended—Electrical Code.

The electrical code adopted in section 9-5(h) is amended and modified in the following respects: (a) None of the informative annexes of the NEC® 2020 have been adopted by the City of Midwest City. (b) Subsection 230-42(d) is amended to read as follows: All residences shall be provided with a minimum service capacity of a one hundred (100) AMP service with three (3) #4 THHN or equivalent in a minimum of one and one-fourth-inch conduit, with a #6 grounding conductor or larger. 230.70(A)(1) Readily accessible location [Amended]. The service disconnecting means shall be installed on the outside of a building or structure nearest the point of entrance of the service conductors. The distance from the point of entrance of a building or structure to the service disconnecting equipment enclosure shall not exceed 24 inches measured horizontally or 60 inches measured vertically. (c) Subsection 310-14, aluminum conductors, is amended to read as follows: All electric conductors installed within the city shall be copper conductors except that in the following two circumstances: 1) aluminum and aluminum-clad aluminum conductors may be used for direct burial or exposed free air installation not located inside structures. Such aluminum and aluminum-clad aluminum conductors shall be terminated outside of the outside walls of a structure. 2) Type AA-8000 Series aluminum conductors may be installed with all following conditions being met: commercial (nonresidential) applications only with services two hundred (200) amp and larger; and strictly installed to the manufacturer's specifications.

(Ord. No. 3560, § 1, 4-23-24)

Ask a question about Midwest City law

Corpus searches the Midwest City sections it holds and shows the ones that match, with their citations. Free, no sign-in.