27.19.054 Electric Central Heating Systems.
(Amended by Ordinances 187432 and 191988, effective January 3, 2025.)
A. Central heating systems of the forced air type must conform to the general installation requirements of this Title. The equivalent kilowatt capacity of such a system must equal the calculated heat loss of the living quarters of the dwelling in B.T.U. per hour, at design conditions, plus not less than 10 percent greater than the total building heat loss in size, when it is the only source of heating. The total output of such a system in B.T.U. must be computed at the location where the thermal (heat) energy is converted and/or transferred to the circulated air.
B. For resistance electric heating elements, the conversion of electric energy to thermal (heat) energy must be considered at an efficiency of 100 percent.
C. For electrically operated heat pump equipment, acceptable evidence of equipment heating performance characteristics must be provided and the equivalent kilowatt capacity determined from it.