27.19.055 Electric Heating - Resistance Cable Type.

(Amended by Ordinance 191988, effective January 3, 2025.)

A.  Resistance cable may not be installed in walls.

B.  Cables may be installed in ceilings or poured masonry floors. Cables may not extend beyond the room in which they originate.  Cables may not be installed in closets, over cabinets that extend to the ceiling, under walls or partitions, or over walls or partitions that extend to the ceiling, except that single runs of cable may pass over partitions where embedded. This requirement does not prohibit low-temperature heat sources in closets to control relative humidity.

C.  Cables must be separated at least eight inches from lighting fixtures, outlets and junction boxes, and two inches from ventilating openings and other such openings in room surfaces, or sufficient area must be provided to assure that no heating cables will be covered by surface mounted lighting units.

D.  A separate manual disconnect must be provided for each space heated.

E.  Thermostatic control must be provided in each heated space, except that no individual thermostatic control may switch any combination of heaters totaling more than seven kilowatts.

F.  Thermostatic controls may not be installed on cable until the wattage has been inspected by a City Administrator and approval posted on the job.