27.19.056 Electric Panel - Prefabricated Conductive Materials.

(Amended by Ordinance 191988, effective January 3, 2025.)

A.  Prefabricated conductive panels may not extend beyond the room in which they originate.

B.  Panels may not be installed on walls.

C.  Panels may be mounted on ceilings.

D.  Panels must be separated at least eight inches from lighting fixtures, outlets, and junction boxes, and two inches from ventilating openings and other such openings in room surfaces, or sufficient area must be provided to assure that no heating panels will be covered by surface mounted lighting units.

E.  A separate manual disconnect must be provided for each space heated.

F.  Thermostatic control must be provided in each heated space, except that no individual thermostatic control may switch any combination of heaters totaling more than seven kilowatts.