Sec. 102-702. - Backflow prevention assembly installation, testing, and maintenance.
(a) A person shall not have an unprotected cross connection, plumbing fixture, equipment, or any other device that allows backflow, or fail to install a backflow prevention device that is required by this article. If a backflow prevention device is required by this article, or any other ordinance, or a retail public utility's service policies, then the water customer shall cause a backflow prevention device to be installed in compliance with the provisions of this article. (1) Each water customer is responsible for the maintenance and repair of each backflow prevention device that is located on the property. (2) Each water customer shall have each backflow prevention device located on their property inspected and tested in accordance with this article, or the retail public utility's cross connection control and back flow prevention program, whichever is stricter. The person performing the inspection and test shall be licensed by the TCEQ as a backflow assembly tester. The licensed tester performing the inspection and testing shall complete a report of each inspection and testing on a form approved by the retail public utility that provides water to the property where the backflow prevention device is located. (3) Each water customer shall cause a TCEQ licensed backflow assembly tester to repair a backflow prevention device that fails a test before returning the backflow prevention device to service. If the backflow assembly tester identifies that the device requires replacement, the replacement shall be performed by a service provider registered with the retail public utility and qualified under this article to perform the work as follows: a. Landscape irrigators can install, replace or repair devices only on residential and commercial lawn sprinkler systems; b. Master plumbers can install, replace and repair devices on domestic residential and commercial plumbing lines and residential and commercial lawn sprinkler systems; c. Fire line contractors can install, replace, and repair devices on fire systems; and d. Individuals licensed by the TCEQ as a backflow assembly tester who are not a landscape irrigator, master plumber, or fire line contractor can only test and repair backflow devices on landscape residential and commercial lawn sprinkler systems. (4) It is the water customer's responsibility to submit, or cause the inspector to submit, the inspection report that is required by this article to the retail public utility providing service to the property within 30 calendar days of the completion of the inspection. Each water customer shall deliver, or cause to be delivered, the annual report of testing and inspection that is required to be performed by this article to the retail public utility that provides water to the property where the backflow prevention device is located no later than 30 days after the date of the inspection and testing. (b) All backflow prevention assemblies shall be tested upon installation by a TCEQ licensed backflow prevention assembly tester and certified to be operating within specifications. (c) Backflow prevention assemblies which are installed to provide protection against health hazards must also be tested and certified to be operating within specifications at least annually by a TCEQ licensed backflow prevention assembly tester. (d) All backflow prevention assemblies shall be installed and tested in accordance with the manufacturer's instructions, the retail public utility's cross connection control and back flow prevention program, and the then-most current edition of The University of Southern California Manual of Cross-Connection Control whichever is stricter. In the event of an irreconcilable conflict between the requirements of The University of Southern California Manual of Cross-Connection Control and the International Building Code as adopted by Section 18-116 of the Code of Ordinances of the City of Brownsville, the stricter requirement shall apply. (e) All failing and/or defective backflow prevention assemblies shall be repaired, overhauled, or replaced at the expense of the customer. It is the customer's responsibility to ensure that all appropriate permits required for the repair, replacement or removal of the backflow prevention assembly are obtained before beginning work. Original forms of such test, repairs, and overhaul shall be kept and submitted to the retail public utility serving the customer, within a reasonable time after receipt of the form, but not more than 30 calendar days after the test, repair or overhaul of each backflow prevention assembly. (f) No backflow prevention assembly or device shall be removed from use, relocated, or other assembly or device substituted without the inspection and approval of the retail public utility serving the customer. Whenever the existing assembly or device is moved from the present location or cannot be repaired, the backflow assembly or device shall be replaced with a backflow prevention assembly or device that complies with this article, the then-current edition of The University of Southern California Manual of Cross-Connection Control and the retail public utility's cross connection control and back flow prevention program, whichever is stricter. In the event of an irreconcilable conflict between the requirements of The University of Southern California Manual of Cross-Connection Control and the International Building Code as adopted by section 18-116 of the Code of Ordinances of the City of Brownsville, the stricter requirement shall apply. (g) Test gauges used for backflow prevention assembly testing shall be tested for accuracy annually in accordance with the then-current edition of The University of Southern California's Manual of Cross-Connection Control. The original gauge accuracy test form must be submitted to the retail public utility serving the customer within a reasonable time after receipt of the form, but not more than 30 calendar days after the gauge has been tested for accuracy.
(Ord. No. 2018-983-DD, pt. 1, 12-4-2018)
Ask a question about Brownsville law
Corpus searches the Brownsville sections it holds and shows the ones that match, with their citations. Free, no sign-in.