Sec. 102-706. - Full flow testing and/or backflow prevention assembly tear down requirements for fire lines.
(a) The Brownsville Public Utilities Board requires backflow prevention assemblies installed on fire-lines to be completely disassembled at a minimum of every five years, if full flow testing cannot be accomplished. The assembly will be cleaned and rubber parts replaced when deemed necessary by the TCEQ licensed backflow prevention assembly tester and/or manufacturer. Assemblies should be appropriately labeled and tagged by the tester to indicate last tear down date. The Brownsville Public Utilities Board Cross Connection Control Department will track individual assemblies over a five year period to ensure provisions are met. (b) A backflow prevention assembly found to be malfunctioning should be completely disassembled, repaired, reassembled and tested by a fire line contractor and certified that the backflow preventer is operating as specified by manufacture's specifications.
(Ord. No. 2018-983-DD, pt. 1, 12-4-2018)