Sec. 13-170. - Installation requirements for backflow prevention assemblies.

(a) General. To ensure proper operation and accessibility of all backflow prevention assemblies, the following requirements shall apply to the installation of these assemblies: (1) Backflow prevention assemblies shall be installed in accordance with the current state environmental regulatory authority's rules and these regulations. The assembly installer must obtain the required plumbing permits, have the assembly tested according to section 13-172 of this article, and have the installation inspected by a representative of the chief plumbing inspector. (2) At those facilities where the local regulatory authority requires a backflow prevention assembly to be installed at the point of delivery of the water supply, such installation of the assembly must be located on private property inside the boundary between the city right-of-way and the landowner's property and located in front of any branch in the line. (3) Any backflow prevention assembly required for premise isolation or firelines for an establishment shall be installed within one hundred (100) feet of the connection to the public water supply. (4) The assembly must be protected from freezing and other severe weather conditions with a city approved enclosure. (5) Lines must be thoroughly flushed prior to installation. A strainer with blowout tapping may be required ahead of the assembly. (6) All backflow prevention assemblies shall be of a type and model approved by the local regulatory authority. (7) All vertical installations of backflow assemblies must have prior approval by the local regulatory authority. Specific make, model, and size for installation must be submitted for approval. (8) Assemblies installed more than five (5) feet above floor level must have a permanent platform for use by testing or maintenance personnel. (9) Bypass lines are prohibited. Pipe fittings which could be used for connecting a bypass line must not be installed. (10) All facilities that require continuous, uninterrupted water service and are required to have a backflow assembly must make provision for the parallel installation of assemblies of the same type so that testing, repair, and maintenance can be performed. (11) The property owner assumes all responsibility for any damages resulting from installation, operation, and/or maintenance of a backflow assembly. The owner shall be responsible for keeping all backflow prevention assembly vaults reasonably free of silt and debris. (12) Upon completion of installation, the local regulatory authority shall be notified, and all assemblies must be inspected and tested in accordance with this article. All assemblies must be registered with the local regulatory authority. Information required for registration shall include, but not be limited to, the date of installation, manufacturer, model, type, size, serial number of the backflow assembly, and initial test report. (b) Reduced pressure principle backflow prevention assemblies (RPs). In the absence of an air gap, RPs must be utilized at premises where a substance is handled that would be hazardous to health if introduced into the potable water system. The RP is normally used in locations where an air gap is impractical. (1) In accordance with the manufacturer's specifications, RPs must be sized to provide an adequate supply of water and pressure for the premises being served. (2) The assembly must be readily accessible for testing and maintenance and must be located in an area where water damage to building or furnishing would not occur from relief valve discharge. The property owner assumes all responsibility for any damage caused by water discharge from an RP assembly. An approved air gap shall be located at the relief valve orifice of RP assemblies. An approved air gap funnel assembly may be used to direct minor discharges away from the assembly This assembly will not control flow in a continuous relief situation. The presence of drain lines to accommodate full relief valve discharge flow is required. (3) No part of a reduced pressure principle backflow prevention assembly shall be submerged in water or installed in a location subject to flooding. (4) Enclosures shall be designed for ready access and sized to allow for the minimum clearances established below. (5) Assemblies two (2) inches and smaller shall have at least six (6) inches clearance on both sides and on top of the assembly, and twelve (12) inches below and behind the assembly. All assemblies larger than two (2) inches shall have a minimum of twelve (12) inches on the back side, twenty-four (24) inches on the test cock side, and the relief valve opening shall be at least twelve (12) inches above the floor or highest possible water level. (6) Any deviations from these requirements must have prior written approval of the local regulatory authority. (c) Reduced pressure principle detector backflow prevention assemblies (RPDAs). RPDAs may be utilized in all installations requiring a reduced pressure principle backflow prevention assembly and detector metering. (1) RPDAs shall comply with the installation requirements for reduced pressure principle backflow assemblies (RPs). (2) The line-size RP assembly and the bypass RP assembly must each be tested. A separate test report for each assembly must be completed by the certified tester. (d) Double check valve backflow prevention assemblies (DCs). DCs may be utilized at premises where a substance is handled that would be objectionable but not hazardous to health if introduced into the potable water system. (1) In accordance with the manufacturer's specifications, DCs must be sized to provide an adequate supply of water and pressure for the premises being served. (2) The assembly shall be readily accessible with adequate room for testing and maintenance. DCs may be installed below grade, providing all test cocks are fitted with brass pipe plugs. All vaults shall be well-drained, constructed of suitable materials, and sized to allow for the minimum clearances established below. (3) Assemblies two (2) inches and smaller shall have at least six (6) inches' clearance below and on both sides of the assembly and, if located in a vault, the bottom of the assembly shall be not more than twenty-four (24) inches below grade. All assemblies larger than two (2) inches shall have a minimum clearance of twelve (12) inches on the back side, twenty-four (24) inches on the test cock side, and twelve (12) inches below the assembly. Headroom of six (6) feet zero (0) inches is required in vaults without a fully removable top. A minimum access opening of thirty-six (36) inches is required on all vault lids. These clearance standards apply to all assemblies installed in vaults, enclosures, and meter boxes. (4) Any deviations from these requirements must have prior written approval of the local regulatory authority. (e) Double check detector backflow prevention assemblies (DCDAs) may be utilized in all installations requiring a double check valve assembly and detector metering. (1) DCDAs shall comply with the installation requirements for double check valve assemblies (DCs). (2) The line-size DC assembly and the bypass DC assembly must each be tested. A separate test report for each assembly must be completed by the certified tester. (f) Pressure vacuum breaker backflow prevention assemblies (PVBs). PVBs may be utilized at point-of-use protection only and where a substance is handled that would be objectionable but not hazardous to health if introduced into the potable water system. PVBs protect against back-siphonage only, and they shall not be installed where there is potential for backpressure. (1) The assembly shall be installed a minimum of twelve (12) inches above the highest downstream piping. (2) PVBs shall not be installed in an area subject to flooding or where damage would occur from water discharge. (3) The assembly shall be readily accessible for testing and maintenance, with a minimum clearance of twelve (12) inches all around the assembly. (4) Any deviations from these requirements must have prior written approval of the regulatory authority. (g) Spill-resistant pressure vacuum breaker backflow prevention assemblies (SVBs). SVBs may be utilized in all installations requiring a pressure vacuum breaker. SVBs shall comply with the installation requirements for pressure vacuum breaker backflow prevention assemblies.

(Ord. No. 11066-2021, § 1, 9-21-21)

Ask a question about Grand Prairie law

Corpus searches the Grand Prairie sections it holds and shows the ones that match, with their citations. Free, no sign-in.