§ 4-30 — Energy conservation code—Amendments
Code of Ordinances of the City of Lewisville, Texas (Supp. No. 34: codified through Ordinance No. 0854-26-ORD, adopted July 6, 2026) · Lewisville City Code § 4-30
Corpus is an independent public-information project, not the official City of Lewisville website. Stable reference: corpuslaw.us/code/9477b4c9-874b-4309-9864-12fe190c7085
Sec. 4-30. - Energy conservation code—Amendments.
The city adopts the following revisions and additions to the International Energy Conservation Code 2021 Edition. It is recognized that the city is located in a warm humid location in Climate Zone 3A of the IECC. Sections C101.1 and R101.1; amend to read as follows: 101.1 Title. This code shall be known as the Energy Conservation Code of the City of Lewisville, and shall be cited as such. It is referred to herein as "this code." Add Sections C102.1.2 and R102.1.2 (N1101.4.1) to read as follows: C102.1.2 Alternative compliance. A building certified by a national, state, or local accredited energy efficiency program and determined by the Energy Systems Laboratory to be in compliance with the energy efficiency requirements of this section may, at the option of the Code Official, be considered in compliance. The United States Environmental Protection Agency's Energy Star Program certification of energy code equivalency shall be considered in compliance. R102.1.2 (N1101.4.1) Alternative compliance. A building certified by a national, state, or local accredited energy efficiency program and determined by the Energy Systems Laboratory to be in compliance with the energy efficiency requirements of this section may, at the option of the Code Official, be considered in compliance. The United States Environmental Protection Agency's Energy Star Program certification of energy code equivalency shall be considered in compliance. Regardless of the program or the path to compliance, each 1- and 2-family dwelling shall be tested for air and duct leakage as prescribed in Section R402.4.1.2 (N1102.4.1.2) and R403.3.3 (N1103.3.3) respectively. Sections C104.2 and R104.2; amend to read as follows: 104.2 Schedule of permit fees. All fees under this code shall be assessed as set forth in the Lewisville City Code, Chapter 2, Section 2-201. Sections C110.1 and R110.1; amend to read as follows: 110.1 Means of Appeal. An individual directly affected by an order, decision, or determination made by the code official relative to the application and interpretation of this code may appeal such order, decision, or determination. In order to hear and decide appeals of orders, decisions, or determinations made by the code official relative to the application and interpretation of this code, the City Council shall act as the Board of Appeals. An appeal must be filed in writing with the City Manager within thirty (30) days after the date of the order, decision, or determination. After receiving an appeal in accordance with this section, the City Manager shall submit the appeal to the City Council for their consideration. The City Council's decision on the appeal shall be the final decision. Section R202 (N1101.6); add the following definition: PROJECTION FACTOR. The ratio of the horizontal depth of the overhang, eave or permanently attached shading device, divided by the distance measured vertically from the bottom of the fenestration glazing to the underside of the overhang, eave or permanently attached shading device. Section R202 (N1101.6); add the following definition: DYNAMIC GLAZING. Any fenestration product that has the fully reversible ability to change it performance properties, including U-factor, solar heat gain coefficient (SHGC), or visible transmittance (VT). Table 402.1.2 (N1102.1.2); amend as follows: CLIMATE ZONE | FENESTRATION U-FACTORf | CEILING U-FACTOR 3 | 0.32 | 0.029 Table 402.1.3 (N1102.1.4) EQUIVALENT U-FACTORS; amend as follows: CLIMATE ZONE | FENESTRATION U-FACTORb,i | CEILING R-VALUE | WOOD FRAME WALL R-VALUE | SLAB R-VALUE & DEPTH 3 | 0.32 | 42 | 19 or 13&3ci h , 0+15ci h | 0 Section C402.5.2; amend to read as follows: C402.5.2 Dwelling and sleeping unit enclosure testing. The building thermal envelope shall be tested in accordance with ASTM E779. ANSI/RESNET/ICC 380, ASTM E1827 or an equivalent method approved by the code official. The measured air leakage shall not exceed 0.30 cfm/ft2 (1.5 Us m2) of the testing unit enclosure area at a pressure differential of 0.2 inch water gauge (50 Pa). Where multiple dwelling units or sleeping units or other occupiable conditioned spaces are contained within one building thermal envelope, each unit shall be considered an individual testing unit, and the building air leakage shall be the weighted average of all testing unit results, weighted by each testing unit's enclosure area. Units shall be tested separately with an unguarded blower door test as follows: 1. Where buildings have fewer than eight testing units, each testing unit shall be tested. 2. For buildings with eight or more testing units, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit enclosure area. For each tested unit that exceeds the maximum air leakage rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Section R402.4.1.4; add a new section to read as follows: R402.4.1.4 Sampling options for R2 multifamily dwelling units. For buildings with eight or more testing units that must be tested as required by R402.4.1.2 or R402.4.1.3, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit enclosure area. For each tested unit that exceeds the maximum air leakage rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Where buildings have fewer than eight testing units, each testing unit shall be tested. Section R403.3.8; add a new section to read as follows: R403.3.8 Sampling options for R2 multifamily dwelling units. For buildings with eight or more testing units that must be tested as required by R403.3.5, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit floor area. For each tested unit that exceeds the maximum duct leakage rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Where buildings have fewer than eight testing units, each testing unit shall be tested. Section R403.6.4; add a new section to read as follows: R403.6.4 Sampling options for R2 multifamily dwelling units. For buildings with eight or more testing units that must be tested as required by R403.6.3, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit floor area. For each tested unit that does not meet the minimum ventilation rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Where buildings have fewer than eight testing units, each testing unit shall be tested. Section R405.2; amend to read as follows: R405.2 Performance-based compliance. Compliance based on total building performance requires that a proposed design meets all of the following: 1. The requirements of the sections indicated within Table R405.2. 2. The building thermal envelope greater than or equal to levels of efficiency and solar heat gain coefficients in Table R402.1.1 or R402.1.3 of the 2009 International Energy Conservation Code. 3. An annual energy cost that is less than or equal to the annual energy cost of the 2021 standard reference design or 8% less than the annual energy cost of the 2018 standard reference design. Energy prices shall be taken from a source approved by the code official, such as the Department of Energy, Energy Information Administration's State Energy Data System Prices and Expenditures reports. Code officials shall be permitted to require time-of-use pricing in energy cost calculations. Exception: The energy use based on source energy expressed in Btu or Btu per square foot of conditioned floor area shall be permitted to be substituted for the energy cost. The source energy multiplier for electricity shall be 3.16. The source energy multiplier for fuels other than electricity shall be 1.1. Section R401.2.5; delete in its entirety. Section R408; delete in its entirety. Section R402.4.6; amend to read as follows: R402.4.6 Electrical and communication outlet boxes (air-sealed boxes). Electrical and communication outlet boxes installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. {remainder deleted.} Section R404.2; delete in its entirety. Table R406.4 (N1106.4); amend to read as follows: TABLE R406.4 (N1106.4) 1 MAXIMUM ENERGY RATING INDEX CLIMATE ZONE | ENERGY RATING INDEX 3 | 63 1 This table is effective until August 31, 2022. TABLE R406.4 (N1106.4) 2 MAXIMUM ENERGY RATING INDEX CLIMATE ZONE | ENERGY RATING INDEX 3 | 59 2 This table is effective from September 1, 2022, to August 31, 2025. TABLE R406.4 (N1106.4) 3 MAXIMUM ENERGY RATING INDEX CLIMATE ZONE | ENERGY RATING INDEX 3 | 57 3 This table is effective from September 1, 2025, to August 31, 2028. TABLE R406.4 (N1106.4) 4 MAXIMUM ENERGY RATING INDEX CLIMATE ZONE | ENERGY RATING INDEX 3 | 55 4 This table is effective on or after September 1, 2028.
(Ord. No. 4037-12-2013, § 5, 12-16-13; Ord. No. 4270-05-2016, § 5, 5-2-16; 0238-20-ORD, § 4, 8-17-20; 0612-23-ORD, § 4, 11-6-23)
Ask a question about Lewisville law
Corpus searches the Lewisville sections it holds and shows the ones that match, with their citations. Free, no sign-in.