3.516 - Accessory Backup Power Generators.

Permanent standby and emergency Backup Power Generators installed as an accessory use at any nonresidential property shall comply with the following standards. Backup Power Generators at Data Centers are governed by Section 3.514. (Data Centers), Subsection M. (Generators and Emergency Power), and are not subject to this Section 3.516 (Accessory Backup Power Generators), except where Section 3.514.M. expressly incorporates these standards by reference. A. Purpose. These regulations govern the placement, installation, screening, and operation of permanently installed commercial Backup Power Generators on nonresidential properties within the City of Mesquite. These regulations apply to all commercial, industrial, institutional, and mixed-use properties, including but not limited to retail establishments, restaurants, medical facilities, warehouse and distribution facilities, Data Centers, and drone delivery staging areas. These regulations are in addition to all applicable requirements of the currently adopted International Building Code, International Fire Code, International Mechanical Code, National Electrical Code, and any other adopted technical code. B. Definitions. See Section 6-102 (Definitions) for the definition of Backup Power Generator - Commercial. C. Permit Requirements. 1. A building permit shall be required for the installation of any Backup Power Generator on a nonresidential property, regardless of the generator's rated capacity. 2. The permit application shall include: a. a site plan or plot plan showing the proposed location of the generator, fuel storage tank (if any), transfer switch, exhaust outlet, and screening enclosure relative to all property lines, buildings, rights-of-way, easements, and adjacent uses; and b. manufacturer's specifications, including rated sound level; and c. fuel system specifications and applicable fire code compliance documentation; and d. electrical permit application; and e. mechanical permit application, where applicable. D. Location and Setback Standards. 1. General. A Backup Power Generator shall not be located: (a) in any required front setback or within any required landscape buffer adjacent to a public right-of-way; (b) in any required fire lane, access easement, or utility easement, unless written approval is obtained from the easement holder; or (c) at any location that obstructs required vehicular sight lines, fire access, or emergency egress. 2. Setback from Residential Uses. A Backup Power Generator shall be located a minimum of fifty (50) feet from the property line of any residentially zoned property or any property used for residential care, nursing home, or similar sensitive use, measured from the outermost edge of the generator unit or its required operational clearance zone, whichever is greater; or such greater distance as may be required to achieve compliance with the noise standards of Subsection F.(Noise Standards). 3. Minimum Setback from Nonresidential Property Lines. A Backup Power Generator shall be set back a minimum of ten (10) feet from any nonresidential property line, unless a greater setback is required by the noise standards of Subsection F.(Noise Standards), or by the applicable building or fire code. 4. Manufacturer clearance distances shall constitute minimum clearances. City setback requirements apply in addition to, not in lieu of, manufacturer clearances. E. Screening and Enclosure. 1. All Backup Power Generators shall be screened from public rights-of-way and from any residentially zoned or used property by one or more of the following: a. Any wall of sufficient height to screen the generator from view at the property line or right-of-way line; b. A manufacturer-supplied or custom-fabricated acoustic enclosure or housing consistent in material and color with the principal building on the site; or c. Evergreen landscaping of sufficient initial height and density to achieve visual screening within two (2) years of installation, in combination with a decorative fence or wall. 2. Screening shall be designed to not impair required maintenance access, ventilation, or combustion air supply to the generator. 3. Screening materials shall be compatible in design and color with the primary structure on the site, as determined by the Director, or designee. 4. A Backup Power Generator installed within an enclosed building or mechanical room that fully conceals the unit from exterior view satisfies the screening requirement of this subsection. F. Noise Standards. 1. No Backup Power Generator shall produce sound levels exceeding the following limits, measured at the receiving property line: a. Sixty-five (65) dB(A) at the property line of any residentially zoned or used property b. Seventy (70) dB(A) at the property line of any nonresidential property 2. The applicant shall demonstrate compliance with noise standards by providing: a. Manufacturer-published sound data at the distances relevant to the site's setback configuration. b. A third-party acoustical analysis prepared by a qualified acoustical engineer, where manufacturer's data is insufficient to confirm compliance at required setback distances. 3. Generator testing and maintenance operations shall be limited to the hours of 7:00 a.m. to 9:00 p.m., Monday through Saturday. Generator testing shall not exceed thirty (30) minutes per test cycle, and no more than two (2) test cycles per calendar month, except as required by law or by the rules of an applicable accreditation or licensing body. 4. Operation of a Backup Power Generator during an actual utility power outage is not subject to the testing hour restrictions of Subsection F.3, but remains subject to the noise level limits of Subsection F.1. 5. City Noise Ordinance. a. Noise from Backup Power Generators shall additionally comply with all applicable provisions of the Mesquite Noise Ordinance, as amended.See Mesquite City Code, Ch. 10, Article III (Noise). In the event of a conflict, the more restrictive standard shall apply. b. Vibrations from Backup Power Generators shall comply with all applicable provisions of the Mesquite City Code, including but not limited to, Ch. 10, Article III (Noise), Sec. 10-71 (Offenses), Subsection (c) (Vibration Offenses); and MZO, Part 1, 1.400, Section 1.407 (Vibration). G. Fuel Storage. 1. All fuel storage associated with a Backup Power Generator shall comply with the currently adopted International Fire Code and applicable NFPA standards for the fuel type. 2. Above-ground fuel storage tanks shall not be located in any required setback, required landscape area, or between the primary building and the public right-of-way. 3. Underground fuel storage tanks require separate permitting in accordance with all applicable state and local regulations. H. Structural Standards. 1. All Backup Power Generators shall be mounted on a concrete pad or engineered foundation designed in accordance with the currently adopted IBC and the manufacturer's specifications. 2. Where a generator is located in an area subject to vehicular traffic or loading, protective bollards or barriers shall be installed to prevent collision damage. I. Nonconforming Generators. 1. Any Backup Power Generator lawfully installed prior to the effective date of the ordinance adding this Section 3.516 (Accessory Backup Power Generators), or 2. A backup power generator project vested prior to the effective date of the ordinance adding this Section 3.516 (Accessory Backup Power Generators), and subsequently lawfully completed within the vesting deadlines, shall be classified as a legal nonconforming installation and shall be subject to the provisions of MZO, Part 1, Section 1.300 (Nonconforming Situations and Amortization of Nonconforming Uses). Such installations shall not be expanded, relocated, or replaced with a generator of greater capacity without full compliance with this Section 3.516 (Accessory Backup Power Generators). Normal maintenance and like-for-like replacement of a non-conforming generator shall not require compliance with these standards, provided the replacement unit does not increase rated capacity by more than ten percent (10%), or increase noise output beyond the pre-existing level. J. Appeals. 1. Appeals to Board of Adjustment. The owner or operator may appeal the director's decision(s) in accordance with MZO, Part 5, 5.200, Section 5.210 (Appeals of Administrative Decisions to Board of Adjustment). See also Appendix D (Comprehensive Fee Schedule), Article XII, Sec. 12-120 (Board of Adjustment Fees), Appeals of Administrative Decisions to the Board of Adjustment. 2. Appeals to the City Council. Appeals to the City Council regarding development documents or development inspections may be made in accordance with MZO, Part 5, 5.100, Section 5.107.P. (Appeals to City Council), and Texas Local Government Code, Chapter 247, Section 247.006 (Appeal) as amended. Development documents and development inspections are defined in MZO, Part 6, 6.100, Section 6.102 (Definitions). See also Appendix D (Comprehensive Fee Schedule), Article XII, Sec. 12-121 (Planning and Zoning Fees), Appeals of Administrative Decisions to the City Council.

(Ord. No. 5259, § 2(Exh. B), 7-20-26)

Ask a question about Mesquite law

Corpus searches the Mesquite sections it holds and shows the ones that match, with their citations. Free, no sign-in.