§ 26-314 — Installation guidelines and requirements for backflow prevention assemblies
Code of Ordinances of the City of Waco, Texas (Supp. No. 88: codified through Ordinance No. 2026-250, enacted April 21, 2026) · Waco City Code § 26-314
Corpus is an independent public-information project, not the official City of Waco website. Stable reference: corpuslaw.us/code/c2c57d13-1894-4b10-92a4-59277c5f79a2
Sec. 26-314. - Installation guidelines and requirements for backflow prevention assemblies.
(a) Generally. To ensure proper operation and accessibility of all backflow prevention assemblies, the following national guideline requirements shall apply to the installation of these assemblies. A permit is required for the installation, replacement or relocation of any backflow prevention device. (1) Backflow prevention assemblies shall be installed in accordance with manufacturer's recommendations, the current TCEQ rules or guidance documents, and these regulations, whichever is the stricter standard. The assembly installer must obtain the required plumbing permits and have the installation inspected by the city. (2) All backflow prevention assemblies shall be installed at a location approved by the city. (3) Assemblies that must be installed or are located on city rights-of-way are the responsibilities of the business or entity that the water line is serving. (4) All backflow prevention assemblies shall be of a type and model approved by the city. (5) All vertical installations of backflow assemblies must have prior approval by the city. (6) The responsible party assumes all responsibility for any damages resulting from installation, operation and/or maintenance of a backflow assembly. (7) Upon completion of installation, the city shall be notified and all assemblies must be inspected and tested. All assemblies must be registered with the city and shall provide the date of installation, manufacturer, model, type, size, serial number of the backflow assembly, and initial test report. (b) Reduced pressure principal backflow prevention assemblies (RPs). Reduced pressure principal backflow prevention assemblies (RPs) may be utilized at premises where a substance is handled that would be hazardous to health if introduced into the potable water system. The RP is normally used in locations where an air gap is impractical. The RP shall be effective against both backsiphonage and backpressure. (1) All RPs must be tested in accordance with this article. Tests are the duty of the responsible party. A permit is required upon installation, replacement or relocation of any backflow prevention assembly. (2) Alternate methods of compliance with these specifications will be evaluated on a case-by-case basis. Any deviations must have prior written approval of the city. (c) Reduced pressure principal detector backflow prevention assemblies (RPDAs). Reduced pressure principal detector backflow prevention assemblies (RPDAs) may be utilized in all installations requiring a reduced pressure principal backflow prevention assembly and detector metering. (1) All DCs must be tested in accordance with this article. Tests are the duty of the responsible party. A permit is required upon installation, replacement or relocation of any backflow prevention assembly. (2) The line-size RP assembly and the bypass RP assembly must each be tested. A separate test report for each assembly must be completed by the certified tester. (d) Double check valve prevention assemblies (DCs). Double check valve backflow prevention assemblies (DCs) may be utilized at premises where a substance is handled that would be objectionable but not hazardous to health if introduced into the potable water system. (1) All DCs must be tested in accordance with this article. Tests are the duty of the responsible party. A permit is required upon installation, replacement or relocation of any backflow prevention assembly. (2) Alternate methods of compliance with these specifications will be evaluated on a case-by-case basis. Any deviations must have prior written approval of the city. (e) Double check detector backflow prevention assemblies (DCDAs). Double check detector backflow prevention assemblies (DCDAs) may be utilized in all installations requiring a double check valve assembly and detector metering. (1) All DCDAs must be tested in accordance with this article. Tests are the duty of the responsible party. A permit is required upon installation, replacement or relocation of any backflow prevention assembly. (2) The line-size DC assembly and the bypass DC assembly must each be tested. A separate test report for each assembly must be completed by the certified tester. (f) Pressure vacuum breaker backflow prevention assemblies (PVBs). Pressure vacuum breaker backflow prevention assemblies (PVBs) may be utilized at point-of-use protection only and where a substance is handled that would be objectionable but not hazardous to health if introduced into the potable water system. PVBs protect against backsiphonage only and shall not be installed where there is potential for backpressure. PVBs cannot be used for premise isolation. (1) All PVBs must be tested in accordance with this article. Tests are the duty of the responsible party. A permit is required upon installation, replacement or relocation of any backflow prevention assembly. (2) Alternate methods of compliance with these specifications will be evaluated on a case-by-case basis. Any deviations must have prior written approval of the regulatory authority.
(Ord. No. 2003-0527, § 1, 9-2-03; Ord. No. 2010-406, § 1, 7-20-10; Ord. No. 2025-477, § 15, 6-17-25)
Ask a question about Waco law
Corpus searches the Waco sections it holds and shows the ones that match, with their citations. Free, no sign-in.