§ 3.23 — Automatic Fire Sprinkler Systems
Code of General Ordinances of the City of Kenosha, Wisconsin (Codified through Ordinance No. 33-26, adopted September 9, 2026. (Supp. No. 11, Update 2)) · Kenosha Code of General Ordinances § 3.23
Corpus is an independent public-information project, not the official City of Kenosha website. Stable reference: corpuslaw.us/code/1b81362e-3d2d-400f-b6c5-5e5aa6192e0c
3.23. - Automatic Fire Sprinkler Systems.
A. Purpose. The purpose of this Section is to provide the means for the automatic extinguishment of fire in buildings or parts of buildings which, because of their size, construction or occupancy, or lack of suitable protective equipment, constitute a special fire hazard to life or property, or an excessive burden upon the fire extinguishing capabilities of the Fire Department. B. Definitions. The following words, terms and phrases, when used in this Chapter, shall have the meanings ascribed to them in this Section, except where the context clearly indicates a different meaning. a. Automatic Fire Sprinkler Equipment means an integrated system of underground and overhead piping designed in accordance with fire engineering standards. The system includes a suitable water supply, such as a gravity tank, fire pump, reservoir or pressure tank and/or connection by underground piping to a municipal water main. The portion of the sprinkler system aboveground is a network of specially sized or hydraulically designed piping installed in a building, structure or area, generally overhead, and to which sprinklers are connected in a systematic pattern. The system includes a controlling valve and a device for actuating an alarm when the system is in operation. The system is usually actuated by heat from a fire and discharges water over the fire area. C. Wisconsin Statutes. All Wisconsin Statutes as they now exist or as they may hereinafter be amended relative to automatic sprinkler systems are incorporated herein by reference and made a part of this Chapter as if fully set forth herein. D. Wisconsin Administrative Code. The provisions of the Wisconsin Administrative Code regulating Automatic Fire Sprinkler Systems and Fire Safety are hereby adopted and incorporated herein by reference as it now exists and as it may be amended in the future. E. Applicability. Every building that is constructed, structurally altered, or has a change of occupancy, where required, shall have an approved Automatic Fire Sprinkler System installed and maintained. F. Plans/Specifications Approval. No Automatic Fire Sprinkler System equipment shall be installed or altered in a building until plans have been submitted to and approved by the Fire Prevention Bureau. a. Automatic Fire Sprinkler Systems Plan Submittal Requirement. Plans and specifications shall accompany each submittal, including all applicable plan review and acceptance testing fees. i. Three (3) copies of the plans and specifications shall be submitted for review. ii. Review: Plans will be reviewed and conditionally approved by the Fire Prevention Bureau. All sprinkler systems require a permit issued by the Department of City Inspections prior to the start of any work. iii. Approval: Approved Plans shall be stamped "Approved By Bureau of Fire Prevention," together with the date of such approval. G. Water Supply System. The water service line providing water to an Automatic Fire Sprinkler System may be connected to the general water service lateral, or may be a separate lateral, providing however, that if connected to the general water service lateral, the line must be separated and valved before the water meter which measures the domestic water supply. The size, location and metering of the required water supply line must be authorized and approved by the Kenosha Water Utility in accordance with the Rules and Regulations governing water service in the City of Kenosha. H. Installation Costs. The owner of any premises requiring Automatic Fire Sprinkler Service is required to pay for the full cost of installing a new or separate fire service water supply line in addition to all necessary valves, fittings and meter settings required to provide such service; and shall further be required to sign a contract for a water supply line service connection with the City of Kenosha Water Utility. I. Fire Department Connections. 1. Requirements. Every Automatic Fire Sprinkler System shall have the following: a. A Concrete Pumper Pad. The concrete pumper pad shall have the following minimum dimensions of concrete: length of twenty (20) feet; width of fifteen (15) feet; and depth of six (6) inches. The concrete pad must be designed and maintained to allow for the parking of at least a Fire Department pumper apparatus of sixty-five thousand (65,000) pounds gross weight on it, without failure. Said pumper pad must have included within it or have within five (5) feet adjacent to it, a fire hydrant containing at least one (1) four and one-half-inch outlet with Kenosha standard threads and at least two (2) two and one-half-inch outlets having national standard threads; if the fire hydrant is located off the concrete pumper pad, the concrete pumper pad must be oriented such that an outlet having the Kenosha standard threads must face the concrete pumper pad, and there may not be any obstruction between the fire hydrant and the pumper pad that would impede a firefighter's access to the fire hydrant from the pumper pad, or that would inhibit the operation of a hose extending from the fire hydrant to the Fire Department pumper apparatus. b. Connection Requirement. The Fire Department Connection shall, unless otherwise prohibited by state law, be operationally connected to the Automatic Fire Sprinkler System. The Fire Department Connection shall have a Siamese connection with two and one-half-inch national standard threads, and a five-inch Storz connection. The Fire Department Connection shall be located to comply with all of the following: no further than five (5) feet from the pumper pad; no further than five (5) feet from a fire hydrant; and no closer to the building it services than the height of the building that it services. There may not be any obstruction between the fire hydrant and the Fire Department Connection that would impede a firefighter's access to the Fire Department Connection, or that would inhibit the operation of a hose extending from the fire hydrant to the Fire Department Connection. There may not be any obstruction between the pumper pad and the Fire Department Connection that would impede a firefighter's access to the Fire Department Connection, or that would inhibit the operation of a hose extending from the pumper pad to the Fire Department Connection. i. Locking Cap Covers. All Fire Department Connections, regardless of when installed, shall be occluded by a Locking Cap capable of being removed by appropriate Key Wrenches carried by the Fire Department. Due to the need for consistency and efficiency in emergency situations, and due to the proprietary nature of Key Wrenches, the Fire Department may specify a certain manufacturer or a limited number of manufacturers that provide Locking Caps removable by a particular Key Wrench configuration. ii. Signage. All Fire Department Connections will be labeled on the building or pumper pad; signage to be approved by the Bureau. iii. Outdoor Rated Horn/Strobe Notifier. An outdoor rated horn/strobe notifier with an excess of one hundred (100) candle power must be installed above the Fire Department connection. c. Bollards. Fire hydrants associated with the pumper pad shall be protected from vehicular traffic damage with bollards. The Bureau must determine the number of bollards needed. d. Exceptions. Any or all of the requirements of this Subsection 3.23.G. may be waived by the Fire Chief in the exercise of his/her discretion, subject to the considerations of public safety and welfare, if either of the following apply: i. The construction, alteration, or change requiring installation of an Automatic Fire Sprinkler System pursuant to Subsection D., herein, creates occupiable space of less than ten thousand (10,000) square feet; or ii. The construction, alteration, or change requiring installation of an Automatic Fire Sprinkler System pursuant to Subsection D., herein, is in sufficiently close proximity to a suitable paved surface, including, but not limited to, a street, and a hydrant to enable the Department to effectively charge an Automatic Fire Sprinkler System from a pumper located on the paved surface. J. Yard Fire Hydrants Requirements. 1. Number of Required Yard Fire Hydrants. Additional yard fire hydrants shall be provided around the perimeter of the building so that no yard fire hydrant is more than five hundred (500) feet from other approved yard fire hydrants measured by normal access routes. 2. Setback Distances. Yard fire hydrants shall be no more than five (5) feet from the curb or edge of the street or fire apparatus access. Alternative setback distances may be considered when site conditions conflict with the provisions of this Section. 3. System Design. a. Valves. Control valves shall be provided to limit the number of yard fire hydrants and/or Automatic Fire Sprinkler Systems affected by maintenance, repair or construction. Valves shall be located at street intersections and at no more than eight hundred (800) foot intervals, and sectional control valves shall be placed so that no more than a combination of yard fire hydrants and Automatic Fire Sprinkler Systems can be isolated between control valves. Valves shall be provided in each yard fire hydrant lead. Valves shall conform to current specifications of the City. b. Outlet Position. All yard fire hydrants shall be positioned so that the largest outlet faces the street or fire apparatus access route. c. Yard Fire Hydrant Height Above Grade. The center of the lowest outlet cap of the yard fire hydrants shall be at least eighteen (18) inches above grade and not more than twenty-three (23) inches above grade. d. Yard Fire Hydrant Specifications. All yard fire hydrants and connecting underground water mains shall meet the specifications of the Kenosha Water Utility. e. Bollards. Yard fire hydrants shall be protected from vehicular traffic damage with bollards. The Bureau shall determine the number of bollards needed. f. Yard Fire Hydrant Colors. i. Yard fire hydrants fed by municipal water shall be red in color. ii. Yard fire hydrants fed by a fire pump shall be painted a solid yellow color, both barrel and caps. iii. No person shall alter the color or paint scheme of an approved private fire hydrant. That person or persons who alter the color of a fire hydrant identified above shall be in violation of this Chapter. K. Testing. The Kenosha Water Utility will require such tests as may be required by applicable NFPA standards. Such tests shall be conducted under the supervision of a water utility representative who shall certify acceptance or rejection of the system. L. Final Approval/Acceptance Test—Automatic Fire Sprinkler System. a. The Automatic Fire Sprinkler System shall have a hydrostatic test performed in the presence of a Fire Department Inspector. b. The Automatic Fire Sprinkler System shall be tested by flows of the main drain and Inspector's test. The installer, in the presence of a Fire Department Inspector, shall conduct the acceptance test. c. The installer shall provide a minimum of three (3) working days advanced notice to the Fire Department prior to performance of the final acceptance test. d. Any work or testing performed on sprinklers and underground supply shall be done by a duly licensed individual. M. Maintenance. The owner or occupant of a building or structure containing a required Automatic Fire Sprinkler System shall maintain the system in an operative condition at all times. The owner or occupant of the building shall properly notify the Fire Chief, or designee thereof, in case such sprinkler protection becomes inoperative due to a breakdown. An Automatic Fire Sprinkler System may not be rendered inoperable, even for servicing, without the written permission of the Fire Chief, or designee, and then only for the duration of the time permitted. No such system, once installed for any reason shall be disconnected or shall cease to be maintained, should a building or structure cease to be occupied, in whole or in part, without first obtaining a permit to do so from the Fire Chief, or designee. Such permit shall not be issued if the building would become an unreasonable fire risk or burden upon the City's firefighting resources, if unprotected. All Automatic Fire Sprinkler Systems shall be tested annually to meet the requirement of NFPA 25. A person(s) or company holding a testers' credential issued by the State of Wisconsin shall perform the tests. N. Certification Inspection/Occupancy. Every installer of an Automatic Fire Sprinkler System shall, upon completion, certify to the Fire Chief, or designee thereof, that installation was completed pursuant to the requirements of this Chapter. Upon receipt thereof, the Fire Chief or designee, will inspect said installation and verify compliance or direct such appropriate action as required to secure compliance. No building or structure for which an Automatic Fire Sprinkler System is required shall be occupied or used for its intended purpose until compliance with this Chapter is verified by the Fire Chief or designee. The Director of City Inspections shall not issue a Certificate of Occupancy for any building or structure until compliance with this Chapter, where required, is verified. O. Penalty. Any person or party violating any provision of this Chapter shall, upon conviction, forfeit a sum not less than one hundred dollars ($100.00) nor more than one thousand dollars ($1,000.00), plus costs and assessments required by law. Each day of violation shall be a separate offense.
(Ord. No. 26-25, § 1, 8-18-2025)
Ask a question about Kenosha law
Corpus searches the Kenosha sections it holds and shows the ones that match, with their citations. Free, no sign-in.