§ 3.24 — Fire Department Standpipes

Code of General Ordinances of the City of Kenosha, Wisconsin (Codified through Ordinance No. 33-26, adopted September 9, 2026. (Supp. No. 11, Update 2)) · Kenosha Code of General Ordinances § 3.24

Corpus is an independent public-information project, not the official City of Kenosha website. Stable reference: corpuslaw.us/code/6d404a96-298d-4c81-ae65-3e3180085033

3.24. - Fire Department Standpipes.

A. Class Three Standpipe. A Class Three Standpipe will be installed in all buildings meeting one (1) or more of the following: 1. Any building of three (3) stories or more. 2. Any building having occupancy of one hundred (100) or more. 3. Any building with one (1) floor of seven thousand five hundred (7,500) square feet or more in area. 4. Any building over one (1) story in height and six thousand (6,000) square feet or more in area on a floor. B. Approved Devices/Materials. All devices and materials used in standpipe systems shall be of approved type. C. Other Standards and Specifications. All other standards and specifications will be taken from the current edition of NFPA Pamphlet #14, "Standards for the Installation of Standpipe and Hose Systems" The installation of a Automatic Fire Sprinkler System will not supersede the requirements for the installation of Fire Department standpipes. D. Parking Structures. Any parking structure built whether aboveground or below ground will have a standpipe system approved by the Bureau prior to installation.

Ask a question about Kenosha law

Corpus searches the Kenosha sections it holds and shows the ones that match, with their citations. Free, no sign-in.