3.26 (Fire Protection Systems) — Fire Protection Systems

Code of General Ordinances of the City of Kenosha, Wisconsin (Codified through Ordinance No. 33-26, adopted September 9, 2026. (Supp. No. 11, Update 2)) · Kenosha Code of General Ordinances § 3.26 (Fire Protection Systems)

Corpus is an independent public-information project, not the official City of Kenosha website. Stable reference: corpuslaw.us/code/6e3b7cc2-4f50-4dfb-9343-3ce631c6f80e

3.26. - Fire Protection Systems.

A. Application For Permit, Plans and Specifications. 1. General. No person may install, erect or construct any Fire Alarm System or Fire Suppression System, or add to, enlarge, move, improve, alter, convert, extend or demolish any existing Fire Alarm System or Fire Suppression System, or cause the same to be done, or commence any work covered by this Code on any Fire Alarm System or Fire Suppression System without first obtaining a Fire Alarm/Fire Suppression System Permit therefor from the Bureau. Such permit shall be issued in the name of the owner. 2. Applications For Fire Alarm/Fire Suppression System Permits. Applications for Fire Alarm/Fire Suppression System Permits shall be filed with the Bureau in writing on a form to be furnished for that purpose. Such application shall describe the property and/or structure upon which the proposed system is to be installed or work done, either by street number, lot, or similar general description which will readily identify and locate the site of the proposed installation or work, and shall show the use or occupancy of all parts of the building and such other pertinent information as may be required by the Bureau. The Bureau Chief or any Inspector of the Fire Department shall, as a condition of granting a Fire Alarm/Fire Suppression System Permit, have the right to enter the premises for which said permit was issued, at any reasonable time during and throughout the course of such work and until final approval thereof has been granted, for the purpose of inspecting said premises and the installation, modification, construction, repair, use and location of Fire Alarm/Fire Suppression Systems. 3. Plans and Specifications. Working plans and specifications showing the location of each component element of the proposed Fire Alarm System and/or Fire Suppression System, all drawings, manufacturers' cut sheets for devices, calculations, material approvals, manufacturers' listed installation and design manuals, pre-engineered design specifications, design specifications, and the manufacturer, model and type of each component element of such systems, shall accompany every application for a permit, and shall be filed in triplicate with the Bureau; provided, however, that the Bureau may authorize the issuance of a permit without plans or specifications for minor or inconsequential work. a. Plans submitted shall be drawn to scale on substantial paper. The submitted plans shall be working plans of sufficient clarity to indicate the nature and character of the work proposed and to show compliance with applicable regulations. Plans shall be prepared in accordance with the provisions of this Code, and shall bear the name of the architect, professional engineer, contractor or other person who prepared them. b. Specifications shall be in detail. Any specifications in which general expressions are used to the effect that "work shall be done in accordance with the Fire Code" or "to the satisfaction of the Bureau" shall be deemed incomplete. Every reference to the Fire Code shall be to the section or subsection applicable to the material to be used or to the method of construction proposed. c. Alterations to and/or modifications of an existing Fire Alarm System and/or Fire Suppression System may not, at the discretion of the Bureau, require a complete set of plans as set forth above; however, each such application for a permit shall include appropriate supporting documentation establishing that the proposed alterations/modifications comply with all appropriate Codes, Ordinances and standards. B. Fire Alarm/Suppression System Permit. 1. Definition. The term approved as used in this Chapter shall mean approval granted by the Chief of the Fire Department or the Bureau under the regulations of this Chapter. 2. Plan Submission and Approval. When plans are required for approval, they shall be submitted in triplicate and work shall not be started until plans are approved, except by special permission to start work as issued by the Bureau. The plans submitted shall be working plans that are clear, legible and permanent. If the application, plans and specifications are in conformity with the requirements of this Code and all other laws or Ordinances applicable thereto, the Bureau shall, upon receipt of the required fee, grant a Fire Alarm/Suppression System Permit for said work and shall sign, date and endorse in writing or by rubber stamp all sets of submitted plans as "approved"; or, if approval is conditioned upon changes to the plan or compliance with other conditions, the plans may be stamped as "conditionally approved." In all such cases where plans are "conditionally approved," the Bureau shall return, with the approved plans, written notification of the conditions that must be satisfied. Whenever a submitted application is incomplete, the Bureau may suspend any action on such application and shall notify the applicant of the information needed to process such application. 3. Modification/Alteration of Approved Plans. Approved plans shall not be changed, and the work shall be installed as shown on the plans. There shall be no modifications or alterations made to approved plans without first obtaining written permission from the Bureau. 4. Permit Term. Fire Alarm/Suppression System Permits shall lapse and become void unless the work authorized thereby is commenced within one (1) year from the date thereof and completed or resumed within one (1) year from the date that construction begins. In the event of further construction after either of the latter of these time periods, a new permit must be obtained pursuant to all the requirements of the Code then in effect. The fees for such new permit shall be based upon the area (square footage of protected area) remaining to be done. 5. Revocation. If the Bureau shall find at any time that any provisions of this Code, the City of Kenosha Code of General Ordinances, laws, orders, plans and/or specifications are not being complied with, it may revoke the Fire Alarm/Fire Suppression System Permit by written notice stating the error or violation which has occurred. Said notice shall be served on the owner and the general contractor or his/her representative on the job; or if there is no general contractor, on the person in charge of the work. Service of the notice shall be by either personal service or by mailing a copy of said notice to the address of said person as known to the Bureau. When any such permit is revoked, it shall be unlawful to do any further work until a new permit is issued, except such work as the Bureau shall order to be done as a condition precedent to issuance of a new permit, or which the Bureau may authorize as reasonably necessary to protect work already done on the job, existing property, adjoining property and the public. Additionally, the Bureau may pursue any other remedies for noncompliance with this Code as such remedies are set forth in the City of Kenosha Code of General Ordinances and/or the Wisconsin State Statutes. 6. Correction of Errors. The issuance or granting of a permit or approval of plans or specifications shall not be deemed or construed to be a permit for, or approval of, any violation of any of the provisions of this Code. If, subsequent to the issuance of a permit, errors are discovered in the application, plans, specifications or execution of the work, the Bureau may require the correction of said errors in said application, plans, specifications or construction. The Bureau may rescind the permit and prevent installation/work operations from continuing when in violation of this Code or any Ordinance of the City of Kenosha. C. Fee Schedule. 1. Scope. The fees fixed in this Chapter shall be assessed and collected by the Bureau for examination and approval of Fire Alarm System Plans and Fire Suppression System Plans. These fees also include the inspection of newly installed/remodeled Fire Alarm Systems and Fire Suppression Systems. These fees are collected in advance from the owner or agent. This fee schedule applies to plan review and inspections of buildings and premises within the City of Kenosha. 2. Plan Examinations. a. Plans showing design and construction details, design computations, and specifications submitted for examination and approval as herein required shall be accompanied by a fee in the amount determined in accordance with this Code. b. For the purpose of determining the fee on the basis of square footage, gross floor area measurements shall be taken from outside of building at each floor level, including basement and other areas affected or serviced by the proposed Fire Alarm System and/or Fire Suppression System. Except as otherwise specified in this Code, the appropriate fee for remodeling or adding to an existing system shall be determined by calculating the square footage of the area to be serviced. 3. Fee Schedule. Failure to obtain a permit before starting work shall result in the fee being doubled. This shall be in addition to any other penalties provided elsewhere in the Code of General Ordinances. Additionally, a penalty of one hundred dollars ($100.00) shall be assessed for each day any work requiring a permit occurs without first obtaining a permit, calculated from the date notice of violation is delivered to either the property owner or contractor performing the work, until such date the owner or contractor submits the proper plans in an approved format to the Bureau. 4. New Systems. Plan Review Fees for new systems shall be determined from time to time by Resolution of the Common Council upon the basis of the total square footage of each building or affected area. D. Plan Resubmittal. A resubmittal fee of one hundred twenty-five dollars ($125.00) shall be assessed for review of Fire Alarm System Plans and Fire Suppression System Plans that have been submitted following initial denial of plan approval, if the resubmission is within eight (8) months of the original denial. A resubmittal fee of fifty dollars ($50.00) shall be assessed for revisions to previously approved plans, and plans that have been previously reviewed, but not denied. E. Alteration/Modifications To Existing Systems. The fee for review of plans to existing systems shall be fifty dollars ($50.00). Submittals with alterations of less than twenty-one (21) sprinklers shall have a fifty dollar ($50.00) fee. For these alterations, the descriptions of the type and scope of work, along with cut-sheets for any new sprinklers, shall be provided. F. Shell Buildings. When an application is submitted for a property where the shell of the building has been completed, the fee will be calculated at fifty (50) percent of the total fee for that particular fee group. When an application is submitted for construction of the interior of a building where the shell of the building has been previously granted a permit, the fees shall be based on the square footage of that space as a percentage of the entire square footage of the subject building and that fee shall be calculated at fifty (50) percent of the total fee for that particular fee group. G. Multiple Identical Buildings. Plans submitted for multiple buildings may be subject to a Multiple Identical Building Fee, which is less than the fee associated with the sum of the individual fees. In order to qualify for the Multiple Identical Building Fee, plans for all buildings shall be submitted at the same time. The fees for the submittal of plans for the first building shall be determined in accordance with the fee schedule established by the Common Council on the basis of the total gross floor area of one (1) building. The fee for each of the remaining identical buildings shall be the higher of either one hundred twenty-five dollars ($125.00) or twenty-five (25) percent of the appropriate fee set forth by the Common Council. H. Certain Devices Subject To A Single Flat Fee. The fee for review of plans for the installation of Fire Protection Systems such as Digital Alarm Communicator Transmitters (DACT), Fire Alarm System Dialers, kitchen hood extinguishing systems, dry chemical extinguishing systems, deluge sprinkler systems which protect openings in fire rate construction, fire detection devices that actuate fire doors/fire shutters, which are not part of any Fire Alarm System, and standpipe systems (not to include combined standpipe systems) shall be one hundred twenty-five dollars ($125.00) for each type of system submitted. However, no additional fee shall be due if such devices are included as a component in a Fire Alarm or Fire Suppression Systems Plan which has been submitted to the Bureau.

Ask a question about Kenosha law

Corpus searches the Kenosha sections it holds and shows the ones that match, with their citations. Free, no sign-in.