15.24.240 - Section 714.1 deleted and replaced to read as follows—Backwater valves.

Section 714.1—Drainage piping serving floor drains or fixtures, which have flood level rims located more than four feet below the elevation of the top rear curb face, shall drain by gravity into the main sewer, and shall be protected from backflow of sewage by installing an approved type backwater valve. The backwater valve shall be installed only in that branch or section of the drainage system which receives the discharge from fixtures. The elevation of the top rear curb face and the proposed elevation of the lowest floor level shall be indicated on the building plans before a plumbing permit will be issued. It shall be the responsibility of the building contractor and/or the building owner to determine the elevation of the lowest floor level.

(Ord. No. 17-24, 8-20-2024)