15.28.230 - Metal conduit or raceway required when.
All wiring exposed on the outside, or exposed on inside concrete or masonry walls of any building within the corporate limits of the city, shall be installed in a metal conduit or raceway system (rigid conduit, intermediate or electrical metallic tubing). All service entrance wires hereafter installed from the public utilities service drop conductors into the building or structure to be served, shall be in an approved metal conduit or raceway system (rigid conduit, intermediate or electrical metallic tubing) equipped at the outer end with a service head fitting. When a mast is required, it shall be at least two-inch galvanized rigid metal conduit. Service laterals may be installed with rigid nonmetallic conduit approved for the purpose. Service drop and lateral installation and meter location shall be in accordance with the power company specifications.
(Ord. 7-90 § 1(15), 1990: Ord. 87-87 § 1 (part), 1987: prior code § 11-2(5))