§ 18-28-706.2 — Mechanical combustion air supply for gas-fired appliances

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-706.2

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/81145115-3791-4313-b9d1-0fbc0dae0c36

18-28-706.2 Mechanical combustion air supply for gas-fired appliances.

Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at the minimum rate of 0.35 ft 3 /min per 1,000 Btu/hr (0.034 mm 3 /kW) for all appliances located within the space.