Sec. 49-1605. - Location of water heaters.
(a) No water heater that depends on the combustion of fuel for heat, shall be installed in the following locations:
(1) In any room used, or designed to be used, for sleeping purposes.
(2) Bathroom.
(3) Clothes closet.
(4) Any other closet or other confined space opening into any bath or bedroom.
(5) Above the ceiling in spaces used as a return air plenum.
(b) A water heater installed above a ceiling or suspended and water heaters installed in R1 and R2 occupancy in other than a centrally located mechanical room shall have a watertight pan installed under the heater as follows:
(1) At least four inches larger than the diameter of the heater.
(2) At least one and one-half inches deep.
(3) At least a three-fourth-inch drain piped independently of the relief valve to an indirect waste. Exception: If the pan drain line is increased to one and one-half-inch, the relief valve may discharge above the one and one-half-inch drain outlet.
(4) Pans installed above the ceiling in spaces used as a return air plenum shall be flame and smoke rated per the applicable building code.
(c) Access and working space for water heaters:
(1) There shall be a clear space in front of the heater equal to the width of the heater plus six inches in both length and width.
(2) There shall be a clear space of at least 18 inches above the heater.
(3) Access to the water heater shall be thru a passageway and/or a door large enough to permit removal of the heater, but not less than 30 inches.
(4) There shall be a minimum clearance as required by the manufacturer, but not less than six inches from the water heater to a wall.
(5) There shall be a minimum clearance as required by the manufacturer, but not less than four inches from a hot water storage tank to a wall.
(6) For water heaters with service ports there shall be minimum clearances for service as follows:
(i) Cleanout opening: 18 inches.
(ii) Manhole opening: 24 inches.
(7) Water heaters with heating bundles shall have a minimum clearance of 18 inches for the inspection and servicing.
(8) All relief valves shall be readily accessible.
(9) The heaters shut-off valve shall be located with a minimum eight inches from the valve to the first fitting downstream of the valve.
(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 51, 8-13-21)