§ 18-29-711.3.1 — Omission of vents for horizontal stack offsets
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-711.3.1
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/f1913f4f-05a9-4f76-9e02-f0a8b10e30f7
18-29-711.3.1 Omission of vents for horizontal stack offsets.
Vents for horizontal stack offsets required by Section 18-29-711.3 shall not be required where the stack and its offset is one pipe size larger than required for a building drain (see Table 18-29-710A, Column 5) and the entire stack and offset is not less in cross- sectional area than that required for a straight stack plus the area of an offset vent as provided for in Section 18-29-915. Omission of offset vents in accordance with this section shall not constitute approval of horizontal branch connections within the offset or within 2 feet (610 mm) above or below the offset.
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
