§ 24-8 — Installation of backflow prevention assemblies for fire sprinkler systems
Municipal Code of the City of Avondale, Arizona (Codified through Ordinance No. 2021-0726, adopted July 6, 2026 (Supp. No. 38, Update 1)) · Avondale Municipal Code § 24-8
Corpus is an independent public-information project, not the official City of Avondale website. Stable reference: corpuslaw.us/code/fdf8eb91-6bf3-485c-8178-6ed15993fce8
24-8 - Installation of backflow prevention assemblies for fire sprinkler systems.
(a) When a backflow prevention assembly is required for a water service connection supplying water only to a fire sprinkler system, the assembly shall be installed at the water service connection in compliance with the standards and specifications adopted by the city. (b) If the Chief of the City of Avondale Fire Department, or his designee, determines that a fire sprinkler system shall have a continuous water supply that may not be interrupted during testing of the backflow prevention assembly, the customer shall install, at his expense, two (2) backflow prevention assemblies parallel to one another at the water service connection. The diameter of each assembly shall be at least equal to the diameter of the water service connection. (c) Modifications of an existing water service connection supplying water solely to a fire sprinkler system shall require the entire system to comply with the standards and specifications adopted by the city. (Ord. No. 1572-315, § 2, 3-16-15)