§ 3-1.202 — Vehicle Impact Protection

Modesto Municipal Code (Supp. No. 72: codified through Ordinance No. 3813-C.S. effective May 12, 2026) · Modesto Municipal Code § 3-1.202

Corpus is an independent public-information project, not the official City of Modesto website. Stable reference: corpuslaw.us/code/2300e912-ccbb-4baa-b44f-f237b977dd77

3-1.202 - Vehicle Impact Protection.

Section 312.2 of the 2025 California Fire Code is hereby adopted by reference, in addition to the following: Posts. Guard posts or other approved means shall be provided to protect storage tanks and connected piping, valves and fittings; dispensing areas; and use areas subject to vehicular damage. When guard posts are installed, the posts shall be: 1. Constructed of steel not less than six (6) inches in diameter and concrete filled, 2. Spaced not more than three (3) feet between posts on center, 3. Set not less than three (3) feet deep in a concrete footing of not less than a fifteen (15) inch diameter, 4. Set with the top of the posts not less than three (3) feet above ground, and 5. Located not less than five (5) feet from the tank.

(Ord. No. 3802-C.S, § 1, effective 1-8-26)