§ 3-1.229 — Electric Disconnects and Photovoltaic (PV) Systems
Modesto Municipal Code (Supp. No. 72: codified through Ordinance No. 3813-C.S. effective May 12, 2026) · Modesto Municipal Code § 3-1.229
Corpus is an independent public-information project, not the official City of Modesto website. Stable reference: corpuslaw.us/code/1d17af15-c45f-4b8b-aa01-8706b05e63be
3-1.229 - Electric Disconnects and Photovoltaic (PV) Systems.
Section 603.4.1 of the California Fire Code is hereby adopted by reference, in addition to: The main electrical service to any commercial building must be accessible for emergency shut-off from the outside of the building. This may be accomplished by providing a (one) main disconnect or a shunt trip device. If a generator system activates automatically when the shunt trip or main disconnect is shut down, a control to stop the generator must be located with the main disconnect or shunt trip. Photovoltaic (PV) power disconnects shall be located with the main electrical disconnect. Shunt trips or main disconnects, PV and generator controls shall be identified by signs approved by the Fire Chief. All disconnects shall not be separated by obstruction or fences. Exception: Electrical control room with a marked door that is accessible from the outside of the building.
(Ord. No. 3802-C.S, § 1, effective 1-8-26)