§ 3-1.209 — Portable Fire Extinguishers

Modesto Municipal Code (Supp. No. 72: codified through Ordinance No. 3813-C.S. effective May 12, 2026) · Modesto Municipal Code § 3-1.209

Corpus is an independent public-information project, not the official City of Modesto website. Stable reference: corpuslaw.us/code/8b7f93d7-7aa6-40df-a475-5d139c49c95a

3-1.209 - Portable Fire Extinguishers.

Section 309 of the 2025 California Fire Code is hereby adopted by reference in addition to the following: Forklifts. All LPG or natural gas driven equipment which operate inside shall have a minimum 1A:10BC fire extinguisher mounted to the equipment and shall comply with Section 906. Section 3504.2.6 of the 2025 California Fire Code is hereby adopted by reference and amended to read as follows: Portable Fire Extinguishers. Not less than one (1) portable fire extinguisher complying with section 906 and with a minimum 2-A:20BC rating shall be provided with ready access within thirty (30) feet of the location where the hot works is being performed and without climbing stairs.

(Ord. No. 3802-C.S, § 1, effective 1-8-26)