§ 8.04.555: Amendment to Appendix B, Fire Flow Requirements for Buildings.
Section B105.4, Land Subdivision Projects, is amended to read as follows: For the subdivision of undeveloped land, due to the undetermined building size and type of construction, the required fire-flow shall be 4,000 gallons per minute (18927 L/min) for duration of four hours with public hydrant spacing of 300 feet. The required fire-flow for the subdivision of land consisting of lots having existing structures shall be in accordance with Table B105.1 for fire-flow and duration. Code reviser's note: Ordinance 1410 adds this section as PMC § 8.04.550 . It has been editorially renumbered to avoid duplication of numbering.
( Ord. 1410 § 2 (Exh. A), 2010 )