For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 8.04.555 — Amendment to Appendix B, Fire Flow Requirements for Buildings

Municipal Code, City of Palmdale, California (Code 2026-05-05) · Palmdale Municipal Code § 8.04.555

Corpus is an independent public-information project, not the official City of Palmdale website. Stable reference: corpuslaw.us/code/a7e511be-e7bb-4a09-acd3-9790e9d25b33

§ 8.04.555: Amendment to Appendix B, Fire Flow Requirements for Buildings.

Section B105.4, Land Subdivision Projects, is amended to read as follows: For the subdivision of undeveloped land, due to the undetermined building size and type of construction, the required fire-flow shall be 4,000 gallons per minute (18927 L/min) for duration of four hours with public hydrant spacing of 300 feet. The required fire-flow for the subdivision of land consisting of lots having existing structures shall be in accordance with Table B105.1 for fire-flow and duration. Code reviser's note: Ordinance 1410 adds this section as PMC § 8.04.550 . It has been editorially renumbered to avoid duplication of numbering.

( Ord. 1410 § 2 (Exh. A), 2010 )

Ask a question about Palmdale law

Corpus searches the Palmdale sections it holds and shows the ones that match, with their citations. Free, no sign-in.