Sec. 18-114. - IBC - Section 902.1.1. Access.

Section 902.1.1. Access, is hereby amended to read as follows: "902.1.1 Access. Automatic fire sprinkler system risers, fire pumps and controllers shall be provided with ready access. Where located in a fire pump room or automatic sprinkler system riser room, the door shall be permitted to be locked provided that the key is available at all times. When automatic fire sprinkler systems are provided within a building and the system serves multiple tenant spaces, the main fire sprinkler control valves shall be placed within an approved room that has access provided directly from the building exterior."

(Ord. No. 4921, § 6, 3-24-2026)