§ 18-115 — IBC - Section 903.1. General

Code of Ordinances of the City of Arvada, Colorado (Supp. No. 67: codified through Ordinance No. 4932, enacted May 5, 2026) · Arvada Code of Ordinances § 18-115

Corpus is an independent public-information project, not the official City of Arvada website. Stable reference: corpuslaw.us/code/f30b4e12-e56f-433a-844b-19a23f2f3bf2

Sec. 18-115. - IBC - Section 903.1. General.

Section 903.1 General, is hereby amended by adding the following subsections: "903.1.2 Location of sprinkler control valves. When automatic sprinkler systems are required within a building and the system serves more than one tenant space, the main control valves shall be located within an approved room that is accessible directly from the building exterior. The door shall be not less than three (3) feet in width by six (6) feet in height." "903.1.3 Fire department access. Any change of occupancy of an existing building that does not have approved fire department access as required in Chapter 5 of the International Fire Code may be required by the fire code official to have an automatic fire sprinkler system installed regardless of the building size." "903.1.4 Multi-tenant buildings. In buildings that have warehouse space(s) that have the ability to allow high-piled combustible storage per Chapter 32 of the International Fire Code shall have a fire line installed with a main that runs the length of the building for future addition of fire sprinkler systems."

(Ord. No. 4921, § 6, 3-24-2026)

Ask a question about Arvada law

Corpus searches the Arvada sections it holds and shows the ones that match, with their citations. Free, no sign-in.