Sec. 18-121. - IBC - Section 1507.2.8.4, Sidewall and other flashing.

Section 1507.2.8.4. Sidewall and other flashing, is hereby added to read as follows: "1507.2.8.4. Sidewall and other flashing. Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. Flashing is required against a vertical front wall, soil stack, vent pipe, chimney, evaporative cooler, skylights and other similar roof openings, and shall be applied in accordance with the asphalt shingle manufacturer's instructions."

(Ord. No. 4921, § 6, 3-24-2026)