§ 16.32.060 — Table 105.5.9 replaced; permit amounts for compressed gases

Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.32.060

Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/7a809b3a-754c-4ed0-a165-68d079232423

Sec. 16.32.060. - Table 105.5.9 replaced; permit amounts for compressed gases.

Table 105.5.9 is replaced with the following table: Table 105.5.9. Permit Amounts for Compressed Gases Type of Gas | Amount (cubic feet at NTP) Carbon dioxide used in equipment operation or processing | 875 (100 lbs.) or remote fill connection Carbon dioxide used in carbon dioxide enrichment systems | 875 (100 lbs.) or remote fill connection Carbon dioxide used in insulated liquid carbon dioxide beverage dispensing applications | 875 (100 lbs.) or remote fill connection Corrosive | 200 Flammable (except cryogenic fluids and liquefied petroleum gases) | 200 Highly toxic | Any amount Inert and simple asphyxiant | 6,000 Oxidizing (including oxygen) | 504 Pyrophoric | Any amount Toxic | Any amount

(Ord. No. O-2026-31, § 1, 6-9-2026)

Ask a question about Longmont law

Corpus searches the Longmont sections it holds and shows the ones that match, with their citations. Free, no sign-in.