§ 308.4 — GREASE HOOD DUCT SYSTEMS, OUTLETS, AND HOODS

Atlanta City Code (Code of Ordinances, Part II) (Supp. No. 108, Update 1: codified through Ordinance No. 2026-37 (26-O-1511), enacted September 30, 2026) · Atlanta Land Development Code, App. D, ch. I, § 308.4

Corpus is an independent public-information project, not the official City of Atlanta website. Stable reference: corpuslaw.us/code/1b82b589-4dec-402a-b65e-d5638e76359f

308.4— - GREASE HOOD DUCT SYSTEMS, OUTLETS, AND HOODS

308.4.1 All grease hood duct systems, including outlet, hoods, and fire extinguishing systems shall be designed in accordance with Vapor Removal from Cooking Equipment - NFPA 96-1987, and Section 502. When fuel burning appliances that are directly vented to outdoors are located in the same room as the hood, negative pressures in the room shall not exceed 0.02 inches water column. The supply of adequate replacement air shall not be dependent upon the opening of windows and doors. 308.4.2 The hood shall be designed with a sufficient air volume to properly exhaust all grease and smoke vapor produced by the equipment which it serves. Unless the hood is designed and certified by a licensed architect or professional engineer or is an approved prefabricated hood tested and certified by the manufacturer, the following requirements shall be met: 1. Canopy-type hoods shall be at least 2 feet deep from bottom edge to top edge of hood and shall overhang the equipment they serve at least 6 inches on all open sides. 2. The bottom edge of a canopy-type hood shall be a maximum of 7 feet above the floor. 3. Canopy hoods open on all sides shall have a minimum exhaust capacity of 150 cfm per square foot of hood area. 4. Canopy-type hoods open on three or less sides shall have a minimum exhaust capacity of 100 cfm per square foot of hood area. 5. Backshelf-type hoods having an intake within 3 feet of vapor producing surface shall have a minimum exhaust capacity of 300 cfm per linear foot of cooking surface within a maximum distance of 1 foot from the face of the hood to the front edge of the equipment they are serving. 6. Provisions shall be made to admit air to the room where the hood is located at a rate not less than that which is exhausted by the hood. SECTION 4: That Chapter 5, Ducts and Duct Systems be amended as follows: (a) That a new Section 501.3 entitled Stratification, be added: 501.3 Stratification "Central heating and/or cooling systems shall have the duct distribution system designed to prevent and/or avoid the stratification of the conditioned air." (b) That Sections 514.1, 514.2, and 514.3 be deleted in its entirety and the following Section 514.1 be submitted in lieu thereof: "All recirculating air systems shall comply with the installation of Air Conditioning and Ventilating Systems, NFPA 90A - 1989." SECTION 5: That Chapter 6, entitled PIPING, be amended as follows: (a) That Section 603.4, Drain Pans, be modified to read as follows: Change "evaporator coils" to read "cooling coils." SECTION 6: VALIDITY If any section, sub-section, sentence, clause or phrase of this ordinance is, for any reason held to be unconstitutional (or invalid) such (holding) shall not affect the validity of the remaining portion of this ordinance. SECTION 7: This ordinance shall become effective upon approval by the Mayor or upon becoming law without approval, except as to cases pending in any court, the previous Heating, Ventilating and Air Conditioning Code of the City of Atlanta shall remain in full force and effect until those cases are finally determined. SECTION 8: All ordinances and parts of ordinances in conflict with this ordinance are hereby repealed.

Ask a question about Atlanta law

Corpus searches the Atlanta sections it holds and shows the ones that match, with their citations. Free, no sign-in.