Section 7.12.8. - Cross Drain Pipes.

A. Minimum Size. Cross drain pipes shall be not less than 15 inches in size when under the street. B. Location. A storm drain pipe running parallel to the existing primary road shall not be located beneath any proposed acceleration/deceleration lanes. The Director of Engineering may modify or waive this requirement if unusual circumstances exist such as topography. C. Inlet and Outlet Ends. The inlet and outlet end of all storm drain pipes, shall have concrete flared end sections, concrete headwalls, or mitered ends with concrete collars or slope-paved headwalls that comply with the standards of Georgia DOT. The collars shall be a minimum of four inches thick and extend 18 inches beyond the limits of the pipe.