§ 6.11.06 — Storm drain pipes
Code of Ordinances of the City of Kennesaw, Georgia (Codified through Ordinance No. 2026-06, enacted March 2, 2026. (Supp. No. 37)) · Kennesaw Municipal Code, App. A, ch. 6, § 6.11.06
Corpus is an independent public-information project, not the official City of Kennesaw website. Stable reference: corpuslaw.us/code/0a664517-79ba-46d6-bf5b-44804dacddfd
6.11.06 - Storm drain pipes.
A. A minimum size of eighteen inch (18") diameter pipe is required under public streets and within City dedicated drainage easements. B. All pipe within City rights-of-way shall be reinforced concrete pipe (RCP) except for the outfall pipe going from the last structure, perpendicular to the roadway, toward the system outfall may be Aluminum Corrugated Metal Pipe (ACMP). C. Minimum wall thickness for ACMP is twelve (12) gauge. D. No ACMP is permitted on a live stream. For the purpose of this requirement live streams are defined as any continuously flowing stream, which intercepts more than a one-quarter (¼) square mile (one hundred sixty (160) acres) drainage area. E. High-density polyethylene pipe (HDPE) pipe will be permitted under the following conditions: 1. Must have granular backfill to the top of the pipe; 2. Depths no greater than ten feet (10') as measured to the invert of the pipe; 3. Installation must be outside of roadway right-of-way; 4. Watertight bell and spigot gasketed joints must be provided; 5. Thirty-six inch (36") diameter or greater must be inspected and certified by a geotechnical engineer or a manufacturer's representative; and, 6. Smoothbore bore pipe only. F. Concrete or solid masonry headwalls of an approved type are required on inlet and outlet ends of the pipe. Steel flared end sections are not permitted. Only concrete flared end sections will be accepted. Standard step bevel end treatment may be approved on large diameter (sixty inches (60") or larger) storm drains where the perimeter is secured with grouted rip-rap or poured in place concrete. G. No ACMP will be permitted if depth as measured to the invert of the pipe is greater than fifteen (15) unless the individual exceptional instance is specifically approved in writing by the Public Works Director or his/her designee. H. Extend outfalls fifty feet (50') beyond the front building setback line for pipes thirty inches (30") or smaller. I. Maximum continuous length of pipe without a point of access (i.e., manhole or junction box) shall be three hundred feet (300') for pipes forty-eight inches (48") and smaller. J. Junction boxes having a manhole-type frame and cover access at grade to the pipe shall be constructed at all changes in horizontal or vertical alignment to meet the requirement of GDOT Standard 1030D. K. The one hundred (100) year headwater pool shall be determined at each proposed and/or modified cross-drainage structure. L. Emergency flow-bypass or emergency overflow relief shall be provided at the elevation of the one hundred (100) year headwater pool to convey flow through (or over) the impoundment structure in instances where the cross drainage structure intercepts a live stream, as defined above.
(Ord. No. 2012-03, 5-7-12)
Ask a question about Kennesaw law
Corpus searches the Kennesaw sections it holds and shows the ones that match, with their citations. Free, no sign-in.
