CB103 — MINIMUM ENERGY EFFICIENCY
Revised Ordinances of Honolulu (2026 S-11: Supplement 11, Ordinance No. 26-1 through Ordinance No. 26-18, June 30, 2026) · Revised Ordinances of Honolulu ch. 16B, § CB103
Corpus is an independent public-information project, not the official City of City and County of Honolulu website. Stable reference: corpuslaw.us/code/c6597769-8e1e-46e5-84d0-957bc9e00358
SECTION CB103 MINIMUM ENERGY EFFICIENCY
CB103.1 Minimum energy efficiency. All buildings shall be designed using ASHRAE Standard 90.1 Appendix G methodology. Buildings shall achieve a savings reduction over baseline in accordance with Table 103.1 without the inclusion of on-site renewable energy or renewable energy purchases. TABLE 103.1MINIMUM ENERGY SAVINGS OVER BASELINE Building Type | % Better Than Standard 90.1-2004 TABLE 103.1MINIMUM ENERGY SAVINGS OVER BASELINE Building Type | % Better Than Standard 90.1-2004 High-Rise Apartment | 49% Mid-Rise Apartment | 60% Hospital | 56% Large Hotel | 38% Small Hotel | 51% Large Office | 55% Medium Office | 53% Small Office | 59% Outpatient Healthcare | 60% Fast Food Restaurant | 24% Full Service Restaurant | 39% Standalone Retail | 66% Strip Mall Retail | 66% Primary School | 65% Secondary School | 63% Non-Refrigerated Warehouse | 73% All Others | 57% CB104.1 General. Buildings shall be designed to comply with this section for the purpose of reducing demand and providing flexibility for the electric grid. CB104.2 Demand responsive controls. All buildings shall provide controls and capability for grid integration through participation in demand response programs in accordance with this section. CB104.2.1 Demand responsive water heating. Electric storage water heaters shall be provided with demand responsive controls in accordance with Table CB104.2.1 or another equivalent approved demand responsive control. Exceptions: 1. Water heaters that provide a hot water delivery temperature of 180°F (82°C) or greater. 2. Water heaters that comply with Section IV, Part HLW or Section X of the ASME Boiler and Pressure Vessel Code. 3. Water heaters that use 3-phase electric power. TABLE CB104.2.1DEMAND RESPONSIVE WATER HEATING Equipment Type | SIZE CATEGORY (input) | Rated Water Storage Volume | Controls Manufactured Before 7/1/2025 | Manufactured on or after 7/1/2025 Electric Storage Water heaters | 12 kW | 40-120 gallons | ANSI/CTA-2045-B Level 1 and also capable of initiating water heating to meet the temperature set point in response to a demand response signal. | ANSI/CTA-2045-B Level 2, except “Price Steam Communication” functionality as defined in the standard. CB104.2.2 Heating and cooling systems controls. Heating and cooling systems shall be provided with controls in accordance with Sections CB104.3.1 through CB 104.3.6. CB104.2.2.1 Demand responsive controls. Buildings shall be provided with demand responsive controls capable of executing the following actions in response to a demand response signal: (a) Automatically increasing the zone operating cooling set point by the following values: 1°F (0.5°C), 2°F (1°C), 3°F (1.5°C), and 4°F (2°C). (b) Automatically decreasing the zone operating heating set point by the following values: 1°F (0.5°C), 2°F (1°C), 3°F (1.5°C), and 4 °F (2°C). (c) Automatically decreasing the zone operating cooling set point by the following values: 1°F (0.5°C), 2°F (1°C). (d) Both ramp-up and ramp-down logic to prevent the building peak demand from exceeding that expected without the DR implementation. Where a demand response signal is not available the heating and cooling system controls shall be capable of performing all other functions. Where thermostats are controlled by direct digital control including, but not limited to, an energy management system, the system shall be capable of demand responsive control and capable of adjusting all thermal setpoints to comply. The demand responsive controls shall comply with one of the following: (a) CB104.2.2.1.1 Air conditioners and heat pumps with two or more stages of control and cooling capacity of less than 65,000 Btu/h. Thermostats for Air conditioners and heat pumps with two or more stages of control and a cooling capacity less than 65,000 Btu/h shall be provided with a demand responsive control that complies with the communication and performance requirements of AHRI 1380. (b) CB104.2.2.1.2 All other HVAC systems. Thermostats for HVAC systems shall be provided with a demand responsive control that complies with one of the following: (1) Certified Open ADR 2.0a VEN, as specified under Clause 11, Conformance. (2) Certified Open ADR 2.0b VEN, as specified under Clause 11, Conformance. (3) Certified by the manufacturer as being capable of responding to a demand response signal from a certified Open ADR 2.0b VEN by automatically implementing the control functions requested by the VEN for the equipment it controls. (4) IEC 62746-10-1. (5) The communication protocol required by a controlling entity, such as a utility or service provider, to participate in an automated demand response program. (6) The physical configuration and communication protocol of CTA 2045-A or CTA 2045-B. Exceptions: 1. Group I occupancies. 2. Group H occupancies. 3. Controls serving data center systems. 4. Occupancies or applications requiring precision in indoor temperature control as approved by the code official. CB104.2.3 Energy storage readiness. Buildings shall comply with one of CB104.2.3.1 or CB104.2.3.2. CB104.2.3.1 Electrical energy storage energy capacity. Each building shall have an ESS with rated energy capacity and rated storage capacity as follows: (a) ESS rated energy capacity (kWh) 1.0 x Installed PV System Rated Power (kWDC). (b) ESS rated power capacity (kW) 0.25 x Installed PV System Rated Power (kWDC) Exception: DC-coupled battery systems shall comply with energy capacity only. CB104.2.3.2 Electrical energy storage system ready. Each building shall have a reserved ESS-ready area to accommodate future electrical storage meeting the following electrical criteria: (a) Energy storage system rated energy capacity (kWh) Area of three largest stories (ft2) x 0.0008 kWh/ft. (b) Energy storage system rated power capacity (kW) Area of three largest stories (ft2) x 0.0002 kW/ft2. CB104.2.3.2.1 ESS-ready location. Each ESS-ready area shall be located in accordance with Section 1207 of the International Fire Code. CB104.2.3.2.2 ESS-ready minimum area requirements. Each ESS-ready area shall be sized in accordance with the designated rating of the planned system UL9540 or UL9540a. Where rated to UL9540a, the spacing shall be per the manufacturer’s instructions. CB104.2.3.2.3 Electrical distribution equipment. The onsite electrical distribution equipment shall have sufficient capacity, rating, and space to allow installation of overcurrent devices and circuit wiring in accordance with NFPA 70 for future electrical ESS installation meeting the criteria of Section CB104.2.3.1. CB104.2.3.2.4 Information on construction documents. Construction documents shall include the following information for ESS systems: (a) Location reserved for inverters, metering equipment, ESS, and a pathway reserved for routing of raceways or conduit from the renewable energy system to the point of interconnection with the electrical service and the ESS. (b) Location and layout of a designated area for ESS. (c) Rated energy capacity and rated power capacity of the installed or planned ESS. CB104.3 Demand Responsive Performance. Buildings shall demonstrate designed and modeled grid integration in accordance with this section. CB104.3.1 Grid Peak Contribution. Buildings shall demonstrate an average reduction in grid-delivered electricity demand during on-peak hours. Buildings shall achieve a Grid Peak Contribution Improvement over baseline in accordance with Table 104.3.1 without the inclusion of on-site renewable energy or renewable energy purchases. The Annual Grid Peak Contribution Improvement shall be calculated using the following equations: [image omitted; see the official code] [image omitted; see the official code] TABLE 104.3.1MINIMUM ANNUAL GRID PEAK CONTRIBUTION IMPROVEMENT OVER BASELINE Building Type | Minimum Annual GPCI TABLE 104.3.1MINIMUM ANNUAL GRID PEAK CONTRIBUTION IMPROVEMENT OVER BASELINE Building Type | Minimum Annual GPCI High-Rise Apartment | 54% Mid-Rise Apartment | 66% Hospital | 61% Large Hotel | 42% Small Hotel | 56% Large Office | 60% Medium Office | 58% Small Office | 65% Outpatient Healthcare | 66% Fast Food Restaurant | 26% Full Service Restaurant | 43% Standalone Retail | 72% Strip Mall Retail | 72% Primary School | 71% Secondary School | 69% Non-Refrigerated Warehouse | 80% All Others | 63% CB104.3.2 Demand Flexibility Capability. Buildings shall demonstrate the ability to reduce net grid-delivered electricity demand averaged over a period of four hours, without changing indoor air temperatures by more than 4°F (2°C). Buildings shall demonstrate a Demand Flexibility Capability (DF) of no less than 10% using the following equations: [image omitted; see the official code]
Ask a question about City and County of Honolulu law
Corpus searches the City and County of Honolulu sections it holds and shows the ones that match, with their citations. Free, no sign-in.