34.30 - Exterior Service Wiring.

All electrical service wiring shall be run in rigid metal conduit, intermediate metallic conduit or electrical metallic tubing. EXCEPTION: Rigid nonmetallic conduit may be approved for the underground part of commercial, industrial, and residential installation in compliance with Article 352 of the 2023 National Electrical Code. Rigid non-metallic conduit is approved for conduits from 400 ampere or less meter sockets that are direct metered, to the electric service panels. Communication equipment under the exclusive control of communication utility companies and outdoor signs having a continuous electrical load with not more than 80% ampacity of the conductors, may be wired with copper #10 AWG ungrounded service conductors and copper # 8 AWG grounded service conductor in 1/2-inch minimum size conduit. (040-25)