34.37 - Conductors.
All conductors smaller than 4/0 AWG, other than aerial service drop conductors, medium and high voltage cables (601-volt insulation level and above), and conductors comprising an integral part of switchboards, transformers or busways meeting N.E.M.A. standards and the provisions of the 2023 National Electrical Code, shall be copper. EXCEPTIONS: #6 AWG minimum aluminum service drop cable or underground cable installed in accordance with the 2023 National Electrical Code may be used for the overhead, aerial service to outside accessory installations such as outbuildings and signs. #4 AWG minimum trade size aluminum conductor may be used as a substitute for copper conductor provided that such aluminum conductors are appropriately sized and further provided that such conductors are terminated in an approved connection. Such conductors shall be used as service conductors or branch panel feeder conductors only. All wiring in outlet or fixture boxes shall be continuous (pigtailed) before the receptacle, fixture or electrical device is installed. (040-25)