Sec. 26-325.12. - Fire sprinkler alarm exterior signals.

Delete section 903.4.3 and insert in lieu thereof the following new section: 903.4.3 Alarms. An approved weather proof audible device suitable for outdoor use with 110 candela visual signal shall be connected to every automatic sprinkler system. The audible device shall be a horn style device that produces a "tri-tone" signal in accordance with NFPA 72 Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. The alarm device(s) shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.

(O.15,861, 16,520)