§ 26-325.9 — Automatic sprinkler systems
Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 26-325.9
Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/6c4954d6-a8dd-4889-bf4d-d3e3d1889208
Sec. 26-325.9. - Automatic sprinkler systems.
(a) Insert the following new section: 903.1.2 Existing Buildings. For other than new construction or where current code contains retroactive provisions an automatic sprinkler system shall be provided pursuant to the provisions of the International Existing Building Code. (b) Delete section 903.2.1.1 and insert in lieu thereof the following new section: 903.2.1.1 Group A-1. An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 6,000 square feet (1115 m2). 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. 4. The fire area contains a multiple-theater complex. (c) Delete section 903.2.1.2 and insert in lieu thereof the following new section: 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 1,500 square feet (1115 m2). 2. The fire area has an occupant load of 50 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. (d) Delete section 903.2.1.3 and insert in lieu thereof the following new section: 903.2.1.3 Group A-3. An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 6,000 square feet (1115 m2). 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. (e) Delete section 903.2.1.4 and insert in lieu thereof the following new section: 903.2.1.4 Group A-4. An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 6,000 square feet (1115 m2). 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. (f) Delete section 903.2.2 and insert in lieu thereof the following new section: 903.2.2 Group B. An automatic sprinkler system shall be provided throughout buildings containing a Group B occupancy where one of the following conditions exists: 1. A Group B fire area exceeds 12,000 square feet (557.5 m2). 2. A Group B fire area is located more than three stories above grade plane. 3. The combined area of all Group B fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (1115 m2). 4. As required by 903.2.2.1 & 903.2.2.2. (g) Delete section 903.2.3 and insert in lieu thereof the following new section: 903.2.3 Group E. An automatic sprinkler system shall be provided throughout stories containing Group E occupancies and throughout all stories from the Group E occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 1,500 square feet (1115 m2). 2. The fire area has an occupant load of 50 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. (h) Delete section 903.2.4 and insert in lieu thereof the following new section: 903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists: 1. A Group F-1 fire area exceeds 6,000 square feet (557.5 m2). 2. A Group F-1 fire area is located more than three stories above grade plane. 3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 12,000 square feet (1115 m2). 4. A Group F-1 occupancy is used to manufacture lithium-ion or lithium metal batteries. 5. A Group F-1 occupancy is used to manufacture vehicles, energy storage systems or equipment containing lithium-ion or lithium metal batteries where the batteries are installed as part of the manufacturing process. (i) Delete section 903.2.7 and insert in lieu thereof the following new section: 903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists: 1. A Group M fire area exceeds 6,000 square feet (557.5 m2). 2. A Group M fire area is located more than three stories above grade plane. 3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 12,000 square feet (2230 m2). (j) Delete section 903.2.9 and insert in lieu thereof the following new section: 903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 6,000 square feet (557.5 m2). 2. A Group S-1 fire area is located more than three stories above grade plane. 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 12,000 square feet (1115 m2). 4. A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m2). 5. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m2). (k) Delete section 903.2.9.1 and insert in lieu thereof the following new section: 903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406.8 of the International Building Code, as shown: 1. Buildings, with a fire area containing a repair garage exceeding 3,500 square feet (325 m2). 2. Buildings with repair garages servicing vehicles parked in basements. 3. A Group S-1 fire area used for the repair of commercial motor vehicles where the fire area exceeds 3,500 square feet (325 m2). 4. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m2).
(O.15,861, 16,317, 16,520)
Ask a question about Des Moines law
Corpus searches the Des Moines sections it holds and shows the ones that match, with their citations. Free, no sign-in.