Sec. 26-325.7. - Penetrations of fire rated walls with coiling overhead fire doors.
Add the following new section: 714.4.1.3. Penetrations for the operation of rolling fire doors. One open ended ½" electrical metallic tubing (EMT) conduit shall be allowed for each rolling overhead fire door to allow the installation of fusible link hardware. The conduit shall be fire stopped where penetrating the wall in accordance with section 714, but the ends shall remain open to allow proper function of the fusible link.
(O.15,861, 16,317)