§ 26-325.16 — Smoke and heat vents
Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 26-325.16
Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/e2c3d538-d9e7-4cb9-aed5-4edfb4b90e13
Sec. 26-325.16. - Smoke and heat vents.
Delete section 910.2.1 and insert in lieu thereof the following new section: 910.2.1 Group F-1 or S-1. Smoke and heat vents installed in accordance with Section 910.3 or a mechanical smoke removal system installed in accordance with Section 910.4 shall be installed in buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 30,000 square feet (2787 m 2 ) of undivided area. In occupied portions of a building equipped throughout with an automatic sprinkler system in accordance with 903.3.1.1, where the upper surface of the story is not a roof assembly, a mechanical smoke removal system in accordance with Section 910.4 shall be installed. Exception: Group S-1 aircraft repair hangers.
(O.15,861)
Ask a question about Des Moines law
Corpus searches the Des Moines sections it holds and shows the ones that match, with their citations. Free, no sign-in.