§ 18-29-904.1.4 — Sidewall vent terminal

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-904.1.4

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/5df3ef7f-f661-47a6-9383-2e9967f5becc

18-29-904.1.4 Sidewall vent terminal.

Vent terminals extending through the wall shall terminate not less than 10 feet (3048 mm) from the nearest abutting lot line and 10 feet (3048 mm) above the highest adjacent grade within 10 feet (3048 mm) horizontally of the vent terminal. Vent terminals shall not terminate under the overhang of a structure with soffit vents. Sidewall vent terminals shall be protected to prevent birds and rodents from entering and blocking the vent opening. (Added Coun. J. 10-14-21, p. 37722, Art. IX, § 3; Amend Coun. J. 12-14-22, p. 58278, Art. VI, § 18)