§ 18-29-903.5 — Vent headers
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-903.5
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/9732a374-3141-48fd-8369-a3c8d507e1dc
18-29-903.5 Vent headers.
Stack vents and vent stacks connected into a common vent header at the top of the stacks and extending to the open air at one point shall be sized in accordance with the requirements of Section 18-29-916.1. The number of fixture units shall be the sum of all fixture units on all stacks connected thereto, and the developed length shall be the longest vent length from the intersection at the base of the most distant stack to the vent terminal in the open air, as a direct extension of one stack. (Amend Coun. J. 10-14-21, p. 37722, Art. IX, § 2)