§ 18-29-901.2 — Trap seal protection
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-901.2
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/b0e19439-2564-4c91-ba34-30d7f64a6783
18-29-901.2 Trap seal protection.
The plumbing system shall be provided with a system of vent piping that will permit the admission or emission of air so that the seal of any fixture trap shall not be subjected to a pneumatic pressure differential of more than 1 inch (25 mm) of water (249 Pa).
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
