Sec. 22-172. - Liquid receivers, shell condensers and other pressure vessels to conform to mechanical engineers code.

(a) The material and construction of liquid receivers, shell condensers, shell coolers, shell evaporators, absorbers, and all other pressure vessels used in refrigerating systems shall be in accordance with the American Society of Mechanical Engineers Code for Unfired Pressure Vessels, current edition. (b) Liquid receivers of direct systems used for air conditioning and for multiple-dwelling systems, except those using class 1 nonirritant and nonflammable refrigerant, shall be of sufficient capacity to contain the total charge of refrigerant. Eighty percent of the net content of shell and tube condenser can be considered as liquid receiver capacity. (c) Every liquid receiver, shell, and tube condenser must be equipped with a means of readily determining the refrigerant content therein.

(Ord. of 7-19-1948, § 52; Code 1958, § 28-20)