Sec. 22-178. - Stop or service valves.

Stop or service valves shall be provided on refrigerating systems in accordance with the following schedules: Class of System Location of valves | A | B | C | D | E Compressor, generator, or other pressure-imposing device | X | X | X | X | X Condenser | X | X | Outlet | Outlet Liquid receiver | X | X | Outlet | Outlet | Outlet Dry evaporator | X | X | Inlet | Inlet | See note (2) Flooded evaporators | X | X | X | X | X Branch headers | X | X | See note (3) (1) Where X is shown in the schedule, valves shall be provided on inlet and outlet refrigerant connections. (2) In a class C and class D system having two or more evaporators in separately refrigerated spaces, valves will be required on both the inlet and outlet of evaporator. (3) Where branch headers are used on a class C or D system with two or more evaporators located in separated refrigerated spaces, valves shall be required on the inlet and outlet of the branch header.

(Ord. of 7-19-1948, § 58; Code 1958, § 28-26)