§ 22-171 — Pressure test requirements
Code of Ordinances of the Town of Cicero, Illinois (Codified through Ordinance No. 71-25, adopted September 23, 2025. (Supp. No. 122)) · Cicero Municipal Code § 22-171
Corpus is an independent public-information project, not the official City of Cicero website. Stable reference: corpuslaw.us/code/cbf3e9c7-726a-437c-86f3-b3169e4485c8
Sec. 22-171. - Pressure test requirements.
(a) All materials used in the construction and installation of refrigerating systems shall be suitable for the refrigerant used, and no material shall be used that will deteriorate due to the chemical action of the refrigerant or the oil or the combination of both. (b) Every part of a refrigerating system shall be designed, constructed, and assembled to withstand safely and without injury the following required test pressures in pounds per square inch: Refrigerant | Symbol | Test Pressure Carbon dioxide | CO 2 | 1500 Ethane | C 2 H 6 | 1100 Propane | C 3 H 8 | 325 Ammonia | NH 3 | 300 Dichlorodifluoromethane | CCL 2 F 2 | 235 Methyl chloride | CH 3 CL | 215 Sulfur dioxide | SO 2 | 170 Isobutane | C 4 H 10 | 130 Butane | C 4 H 10 | 90 Dichlorotetrafluoroethane | C 2 CL 2 F 4 | 80 Ethyl chloride | C 2 H 5 CL | 60 Methyl formate | C 2 H 4 O 2 | 50 Dichloroethylene | C 2 H 2 CL 2 | 50 Trichloromonofluoromethane | CCL 3 F | 50 Dichloremethano | CH 2 CL 2 | 30 (c) Where the low pressure side of class A systems are protected by a safety valve, the test pressure shall be twice the pressure at which the safety valve is set. (d) Castings used in the manufacture of compressors and other parts of refrigerating systems shall be sufficient thickness and close-grain structure to prevent porosity.
(Ord. of 7-19-1948, § 51; Code 1958, § 28-19)
Ask a question about Cicero law
Corpus searches the Cicero sections it holds and shows the ones that match, with their citations. Free, no sign-in.