Sec. 22-173. - Coils; tubing sizes.

(a) Refrigerant-containing parts of coils shall have not less than 34/1000 of an inch wall thickness for tubing sizes three-fourths inch outside diameter or smaller. For outside diameters over three-fourths inch, the wall thickness shall be increased in the ratio of the new diameter to three-fourths inch. (b) Unless coils are constructed of a nonferrous metal, they shall be protected against corrosion by an approved process. All connections shall be welded or brazed. Solder used for brazing shall have a melting point of at least 1,000 degrees.

(Ord. of 7-19-1948, § 53; Code 1958, § 28-21)