Sec. 18-175. - Fill pipe requirements.

Fill pipes shall be carried to a location outside of any building, as remote as possible from any doorway or other opening into any building and in no case closer than five feet from any such opening. (a) Location shall be in a place where there is a minimum danger of breakage from trucks or other vehicles. (b) Each fill pipe shall be closed by a screw cap, or other tight fitting cap. The cap thereof shall be locked at all times when filling or gauging process is not going on. Unloading hose from tank hose into underground tank shall be metallic lined or its equivalent and shall be equipped with a non-ferrous nozzle or tight connection metal nipple.

(Ord. No. 5502, § 10, 7-7-70)