Sec. 18-179. - Greasing pits.
Every greasing pit installed within a building, or enclosed by three or more walls, shall be ventilated by a vent duct not less than six inches in diameter (or equivalent cross-sectional area if a non-circular duct is used). Duct shall start within four inches of the floor and shall be extended on an upward diagonal or by an easy bend over to the sidewall, thence straight up through roof to a height sufficient to draw off gasoline vapors which may accumulate in bottom of pit. Floor of pit should pitch lightly toward corner where duct is located, to facilitate flow of gases to duct. (a) Gasoline or naphtha shall never be used to clean out any pit, whether pit is located within a building or enclosure, or outside in the open. (b) If electrically lighted, globes shall be of vaporproof construction and wiring in conduit. (c) If sewer connection is provided, an adequate grease trap shall be provided to intercept greases and oils. Traps shall be cleaned out at least every thirty days.
(Ord. No. 5502, § 14, 7-7-70)