§ 5-908 — International Mechanical Code—Table 307.2.2 amended

Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 5-908

Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/e8824fd7-ef98-4ed5-b37a-506054efe411

Sec. 5-908. - International Mechanical Code—Table 307.2.2 amended.

Table 307.2.2, condensate drain sizing, of the 2018 International Mechanical Code is hereby amended to read as follows: Table 307.2.2. Condensate Drain Sizing Equipment Capacity | Minimum Condensate Pipe Diameter Up to 5 tons of refrigeration | ¾ inch Up to 7½ tons of refrigeration | 1 inch Up to 50 tons of refrigeration | 1½ inches Up to 170 tons of refrigeration | 2 inches Up to 300 tons of refrigeration | 3 inches One inch = 25.4 mm, one ton = 3.517 kW.

(Code 2018, § 5-608)